It integrates a 10 A thermal-magnetic circuit breaker (C-curve, magnetic trip 5–10 x In) with a 30 mA residual-current detection element, all in a 36 mm wide clip-on housing for DIN-rail mounting. Rated 10 A at 230 V AC, 50 Hz, with a breaking capacity of 6000 A Icn per EN/IEC 61009-2-1. The C-curve means the magnetic trip operates between 5 and 10 times rated current — 50 to 100 A — so it handles moderate inrush from motorized or capacitive loads without nuisance tripping, while still clearing short circuits within the 6 kA limit. The 30 mA earth-leakage sensitivity protects against indirect contact and provides supplementary protection against direct contact in TN and TT systems.
Terminals accept 1–16 mm² rigid or 1–10 mm² flexible conductors; strip length 15 mm, tightening torque 2 N.m.
No known end-of-life notice or successor part — this is the standard RCBO for the iDPN Vigi family.