Specifications

A9D64845 key specifications
ParameterValue
Control typeToggle
Network typeAC
Product or component typeResidual current breaker with overcurrent protection (RCBO)
Voltage400 V AC 50/60 Hz
[Ue] rated operational voltage230/240 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage4 kV
[Icw] rated short-time withstand currentIcw: 250 A during 8/20 µs impulse withstand
Breaking capacity6000 A Icn at 240 V AC 50/60 Hz
Current45 A at 50 °C
Residual current tripping technologyVoltage dependent
[Ics] rated service breaking capacity6000 A at 240 V AC 50/60 Hz
Network frequency50 Hz

All specifications

A9D64845 additional specifications
ParameterValue
Poles description1P + N
Number of protected poles1
IP degree of protectionIP20
Mounting modeClip-on
Mounting supportDIN rail
Wire stripping lengthPower circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection
Connections - terminalsScrew clamp terminal (top) 1...25 mm² rigid without cable end Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...16 mm² rigid without cable end Screw clamp terminal (bottom) 1...10 mm² flexible
Relative humidity95 % at 55 °C
Depth77.5 mm
Width18 mm
ColorWhite
Height110 mm
Product weight205 g
Electrical durability5000 cycles
Mechanical durability20000 cycles
StandardsIEC 61009-1 IEC 61009-2-2
RangeActi9
Curve codeC
9 mm pitches2
Earthing systemTN
Tropicalisation2
Limitation class3
Local signallingON/OFF indication
Neutral positionLeft
Device short nameiC60N RCBO
Tightening torquePower circuit: 3.5 N.m top Power circuit: 2 N.m bottom
Trip unit technologyThermal-magnetic
Earth-leakage protectionIntegrated
Provision for padlockingPadlockable with padlock Ø 4 mm
Device location in systemOutgoer
Earth-leakage sensitivity30 mA
Suitability for isolationYes
Contact position indicatorYes
Circuit breaker applicationDistribution
Locking options descriptionON/OFF locking facilities
Earth-leakage protection classType A
Ambient air temperature for storage-40...85 °C
Earth-leakage protection time delayInstantaneous
Ambient air temperature for operation-15...60 °C
Comb busbar and distribution block compatibilityNO
MPN