Rated 6 A with a B curve (magnetic trip 3–5 x In) and 6 kA breaking capacity at 230 V AC, 50 Hz, it protects a single outgoing final circuit against overload, short-circuit, and earth faults. The integrated residual-current element trips at 300 mA sensitivity, so it's sized for basic fault protection (not supplementary personal protection — that needs 30 mA). Neutral is on the left, phase on the right. Terminals accept 1–16 mm² rigid or 1–10 mm² flexible; strip 15 mm and torque to 2 N·m. The toggle shows ON, OFF, and fault-trip positions, so a quick glance tells you whether it's a manual off or a real trip.
The 6 kA Icn at 230 V AC meets EN/IEC 61009-2-1 for domestic and light commercial distribution boards; if your fault level exceeds that, you'll need a higher-breaking upstream device (e.g. a 10 kA or 15 kA MCB).
Compliance documentation
The Acti9 range carries CE marking and is RoHS compliant. Specific REACH and UL documentation is available on request with the RFQ.