Skip to main content
Schneider Electric A9D68620 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D68620 Acti9 iDPN Vigi, 20 A, 6 kA, 300

MPNA9D68620
Obsolete

Schneider Electric Acti9 iDPN Vigi RCBO, 1P+N, 20 A, 6 kA, 300 mA, Curve B, DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9D68620 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
A9D68620 — Electrical Ratings
ParameterValue
Rated current (In)20 A
Rated operational voltage (Ue)220...240 V AC 50 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability20000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D68620 — Identification
ParameterValue
Product nameActi9 iDPN Vigi
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiDPN N Vigi
A9D68620 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsSingle terminal top or bottom 1...16 mm² rigid Single terminal top or bottom 1...10 mm² flexible Single terminal top or bottom 1...10 mm² flexible with ferrule
Wire stripping length15 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width36 mm
Height85 mm
Depth73 mm
A9D68620 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity95 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9D68620 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

The A9D68620 is a Schneider Electric Acti9 iDPN Vigi residual-current circuit breaker with overcurrent protection (RCBO) in a 1P+N format, rated 20 A with a 6 kA breaking capacity at 230 V AC and 300 mA earth-leakage sensitivity, Curve B. The kit is complete — no separate RCD module or add-on needed; the earth-leakage protection is integrated into the same housing.

The 20 A rated current (In) and 6 kA Icn at 230 V AC define the maximum continuous load and the fault-clearing capability. The 300 mA earth-leakage sensitivity is set for protection against insulation faults, not direct human contact — that is a 30 mA threshold. The thermal-magnetic trip unit handles both overload (thermal bimetal) and short-circuit (solenoid) conditions. The 20,000-cycle electrical and mechanical endurance matches typical panel duty for a distribution outgoer.

Clip-on mounting on standard DIN rail (35 mm). The 9 mm connection pitch between phase and neutral matches the Acti9 busbar system. IP20 on the front, IP40 inside a modular enclosure — standard for indoor distribution boards.

Sourcing this order code

No minimum order quantity is imposed for this line. The part is fully specified for BOM inclusion — the 20 A, 6 kA, 300 mA, Curve B combination is a standard configuration for final-distribution RCBOs in commercial and light-industrial panels.

Frequently asked questions

Where can I buy A9D68620 and how do I get a price?

The A9D68620 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the closest pin-compatible alternative to A9D68620 in this component family?

Within the Acti9 iDPN Vigi family, the closest alternatives differ by rated current (e.g., 16 A or 25 A) or earth-leakage sensitivity (e.g., 30 mA). No exact pin-compatible alternative with the same 20 A, 6 kA, 300 mA, Curve B specification exists in the same series — the A9D68620 is the only order code matching that exact combination.

What is A9D68620's listed depth (73 mm) on this component line?

The A9D68620 has a depth of 73 mm, a width of 36 mm, and a height of 85 mm.

What is A9D68620's listed range (Acti9) on this component line?

The A9D68620 belongs to the Schneider Electric Acti9 range, specifically the iDPN Vigi series of combined MCB/RCCB (RCBO) devices.

What compliance documentation does this brand provide for A9D68620 (RoHS, REACH, UL, IEC)?

The A9D68620 is designed to EN/IEC 61009-2-1 and carries tropicalisation class 2 per IEC 60068-1. The evidence does not list RoHS, REACH, or UL documentation specifically for this order code.

MPN
A9D68620