The integrated earth-leakage element trips at 300 mA sensitivity, covering personnel protection and fire-risk mitigation on final subcircuits. Breaking capacity is 6000 A Icn at 220–240 V AC, 50 Hz, certified to EN/IEC 61009-2-1.
Neutral is on the left, phase on the right — verify orientation before snapping onto the rail. Terminals accept 1–16 mm² rigid or 1–10 mm² flexible; strip length 15 mm, tighten to 2 N·m. The 9 mm connection pitch between phase and neutral matches standard Acti9 busbar spacing. IP20 on the body, IP40 inside the modular enclosure — fine for distribution boards, not for washdown areas.