A9D87432 key specifications
ParameterValue
Control typeToggle
Network typeAC
Product or component typeResidual current breaker with overcurrent protection (RCBO)
Voltage500 V AC 50 Hz
[Ue] rated operational voltage380...415 V AC 50 Hz
[Uimp] rated impulse withstand voltage4 kV
Surge current250 A
Breaking capacity6000 A Icn at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1 6 kA Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2
Current32 A
Residual current tripping technologyVoltage independent
[Ics] rated service breaking capacity6000 A 100 % x Icn at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1 6 kA 100 % x Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2
Network frequency50 Hz

All specifications

A9D87432 additional specifications
ParameterValue
Poles description4P
Number of protected poles4
IP degree of protectionIP40 (distribution enclosure) conforming to IEC 60529 IP20 conforming to IEC 60529
Mounting modeClip-on
Mounting supportDIN rail
Connection pitch9 mm between poles
Wire stripping length12 mm for top or bottom connection
Connections - terminalsTunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible Tunnel type terminal top or bottom 1...25 mm² flexible with ferrule
Relative humidity95 % at 55 °C
Depth78 mm
Width72 mm
ColorWhite
Height86 mm
Electrical durability10000 cycles
Mechanical durability20000 cycles
StandardsEN/IEC 60947-2 EN/IEC 61009-2-1
RangeActi9
Curve codeB
9 mm pitches8
Quality labelsIMQ VDE NF KEMA-KEUR
Tropicalisation2
Limitation class1 conforming to EN/IEC 61009-2-1
Local signallingON, OFF, fault trip
Device short nameiC60 RCBO
Tightening torque2 N.m
Device applicationDistribution
Overvoltage categoryIII conforming to IEC 60364
Trip unit technologyThermal-magnetic
Magnetic tripping limit3...5 x In
Earth-leakage protectionIntegrated
Device location in systemOutgoer
Earth-leakage sensitivity30 mA
Suitability for isolationNo conforming to IEC 60947-1
Contact position indicatorNo
Electromagnetic compatibility8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1
Earth-leakage protection classType A
Rated breaking and making capacityIdm 6000 A at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1
Ambient air temperature for storage-40...70 °C
Earth-leakage protection time delayInstantaneous
Ambient air temperature for operation-25...60 °C
Comb busbar and distribution block compatibilityTop or bottom: YES Bottom: biconnect