Clip-on mounting to DIN rail (EN 60715) and a 9 mm phase-to-neutral pitch keep the panel layout compact. The thermal-magnetic trip unit needs no external power; the toggle gives local ON/OFF/fault-trip indication.
Installation and wiring
Terminals accept 1...16 mm² rigid or 1...10 mm² flexible wire; strip length 15 mm. IP20 on the body, IP40 inside the modular enclosure; the unit is not rated for washdown environments. Rated for 50 Hz networks only. Electrical and mechanical durability are each 20,000 cycles — adequate for a distribution outgoer that sees infrequent switching. Tropicalisation class 2 (IEC 60068-1) and 95 % RH at 55 °C cover humid installation environments.