Schneider Electric A9D99616 — Residual Current Breakers (RCCB/RCBO)

Schneider A9D99616 Acti9 iDPN Vigi RCBO, 16A C-curve 30mA

MPNA9D99616
Obsolete

Schneider Electric Acti9 iDPN Vigi, RCBO, 1P+N, 16 A, C-curve, 30 mA, 6 kA, clip-on DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9D99616 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
A9D99616 — Electrical Ratings
ParameterValue
Rated current (In)16 A
Rated operational voltage (Ue)220...240 V AC 50 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability20000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D99616 — Identification
ParameterValue
Product nameActi9 iDPN Vigi
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiDPN N Vigi
A9D99616 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsSingle terminal top or bottom 1...16 mm² rigid Single terminal top or bottom 1...10 mm² flexible Single terminal top or bottom 1...10 mm² flexible with ferrule
Wire stripping length15 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width36 mm
Height85 mm
Depth73 mm
A9D99616 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity95 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9D99616 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

The Schneider Electric A9D99616 is an Acti9 iDPN Vigi residual-current circuit breaker with overcurrent protection (RCBO) — a single-module device combining a 16 A thermal-magnetic MCB and a 30 mA earth-leakage trip in one 1P+N unit. The 16 A rated current (In) and C-curve magnetic trip (5–10 × In) mean it handles general-purpose lighting and socket circuits where inrush from small motors or fluorescent ballasts stays under 160 A peak before the magnetic coil clears it. The 30 mA sensitivity covers personnel protection (indirect contact and additional fire protection per IEC 60364). Breaking capacity is 6000 A Icn at 220–240 V AC 50 Hz, certified to EN/IEC 61009-2-1 — adequate for most residential and light commercial distribution boards where the prospective short-circuit current at the outgoer does not exceed 6 kA. The limitation class 3 rating means it restricts let-through energy under fault conditions, reducing stress on downstream wiring.

Clip-on mounting to DIN rail (EN 60715), 36 mm width (4 × 9 mm pitches). Terminals accept 1–16 mm² rigid or 1–10 mm² flexible (with or without ferrule); strip length 15 mm, torque 2 N·m.

Environmental and compliance details

Rated for pollution degree 3 (industrial or damp environments), overvoltage category III (distribution board level), and tropicalisation class 2 per IEC 60068-1 (handles 95 % RH at 55 °C). Mechanical and electrical durability are both rated at 20 000 cycles — the toggle switch and internal mechanism are matched for that service life.

Frequently asked questions

What is the breaking capacity of the A9D99616?

The breaking capacity is 6000 A Icn at 220–240 V AC 50 Hz, certified to EN/IEC 61009-2-1.

What does the C-curve mean on this RCBO?

The C-curve magnetic trip operates at 5 to 10 times the rated current (80–160 A for this 16 A unit), suitable for circuits with moderate inrush like small motors or fluorescent lighting.

Where can I buy the A9D99616 and what is the lead time?

The A9D99616 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time; no stock count or lead-time number is published here.

MPN
A9D99616