It combines a 13 A thermal-magnetic trip (curve C, magnetic trip 5–10 × In) with integrated 30 mA earth-leakage protection in a single DIN-rail module. Rated breaking capacity is 10 kA Icn at 400 V AC, 50/60 Hz, per EN/IEC 61009-2-1, which covers the majority of commercial and light industrial distribution boards where the prospective fault current stays under that threshold. This is a current-production part (lifecycle stage: current) from the Acti9 range, designed for outgoing feeder protection in AC networks.
The 13 A rated current (In) and curve C (5–10 × In magnetic trip) mean this RCBO is sized for general-purpose circuits feeding socket outlets, lighting, or small loads where moderate inrush is expected — not for motor starting or heavy inductive loads that would need a D curve. The 30 mA earth-leakage sensitivity provides additional protection against electric shock in circuits where the standard is required (e.g., socket circuits in many IEC countries). For panels with a higher prospective short-circuit current, upstream current-limiting devices or a higher-rated breaker would be needed. IP20 on the device body, IP40 in a modular enclosure — fine for dry indoor panels, not for washdown environments.
Installation and wiring notes
Clip-on DIN-rail mount, neutral on the left. Tunnel terminals accept 1–16 mm² rigid or 1–10 mm² flexible cable; tighten to 2 N·m. Strip 14 mm. The 18 mm phase-to-phase pitch and 9 mm phase-to-neutral pitch are standard for the Acti9 range — busbars and comb connectors fit directly. Local signalling shows fault indication and ON/OFF status on the toggle. Electrical and mechanical durability are both rated at 20,000 cycles — adequate for normal switching duty in a distribution board; not intended for frequent manual switching as a disconnect.