Skip to main content
Schneider Electric A9DC7725 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9DC7725 Acti9 iCV40 RCBO, 25 A, 30 mA, C

MPNA9DC7725
Active

Schneider Electric Acti9 iCV40N RCBO, 25 A, 300 mA, C-curve, 3P+N, 6 kA Icn at 400 V AC, DIN-rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Residual Current Protection

A9DC7725 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationFault indication ON/OFF indication

Electrical Ratings

A9DC7725 — Electrical Ratings
ParameterValue
Rated current (In)25 A
Rated operational voltage (Ue)400 V AC 50/60 Hz
Poles description3P + N
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)440 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability20000 cycles
Mechanical durability (operating cycles)20000 cycles

Identification

A9DC7725 — Identification
ParameterValue
Product nameActi9 iCV40
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiCV40N

Mechanical

A9DC7725 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules10
Terminal connectionsTunnel type terminals top or bottom 1...16 mm² rigid Tunnel type terminals top or bottom 1...10 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width90 mm
Height93 mm
Depth73 mm

Environmental

A9DC7725 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity95 % at 55 °C
Operating altitude2000 m

Approvals

A9DC7725 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

The Schneider Electric A9DC7725 is an Acti9 iCV40N residual-current circuit breaker with overcurrent protection (RCBO) — a combined MCB and RCD in a single 3P+N module, rated at 25 A with a 300 mA earth-leakage sensitivity and a C-curve magnetic trip characteristic (5 to 10 × In).

The 25 A rated current (In) and C-curve mean this RCBO is sized for general-purpose lighting and socket-outlet circuits where inrush from small motors or fluorescent ballasts is expected — the C-curve holds through 5 to 10 times In before magnetic tripping, so it avoids nuisance trips on moderate starting surges. The breaking capacity (Icn) is 6000 A at 400 V AC, 50/60 Hz, conforming to EN/IEC 61009-2-1. The integrated earth-leakage protection trips when leakage exceeds 300 mA.

Tunnel-type terminals accept 1 to 16 mm² rigid or 1 to 10 mm² flexible conductors; tightening torque is 2 N·m. Wire stripping length is 14 mm for both top and bottom connections. IP20 rated (finger-safe) on the front face; IP40 in a modular enclosure — suitable for installation inside a distribution board where the enclosure provides the environmental seal.

Frequently asked questions

What is the breaking capacity of A9DC7725?

The breaking capacity (Icn) is 6000 A at 400 V AC, 50/60 Hz, conforming to EN/IEC 61009-2-1.

What is the earth-leakage sensitivity of A9DC7725?

The integrated earth-leakage protection trips at 300 mA residual current.

What compliance standards does A9DC7725 meet?

It is certified to EN/IEC 61009-2-1, carries VDE and EAC quality labels, and is rated for overvoltage category III per IEC 60364 and pollution degree 3.

MPN
A9DC7725