Rated 32 A with a C-curve magnetic trip (5...10 x In) and a 6 kA Icn breaking capacity at 400 V AC, it integrates 300 mA earth-leakage protection in a single 3P+N module. The thermal-magnetic trip unit handles both overload and short-circuit; the integrated RCD covers ground faults.
The 32 A rated current and C-curve (5–10 x In magnetic trip) suit it for mixed resistive and moderate-inductive loads — lighting banks, small motor circuits, socket outlets. Limitation class 3 (energy let-through) helps with downstream coordination. The 300 mA earth-leakage sensitivity is a standard for general distribution, not personal shock protection (30 mA would be required for that). The 3P+N configuration with neutral on the left is fixed — verify busbar and panel layout before specifying. The 18 mm phase-to-phase pitch and 9 mm phase-to-neutral pitch match standard Acti9 distribution boards. Clip-on DIN-rail mounting (EN 60715) and tunnel terminals accepting 1...16 mm² rigid or 1...10 mm² flexible wire simplify panel assembly.
Designed to EN/IEC 61009-2-1 (RCBO standard). Carries VDE and EAC quality marks. IP20 on the terminals, IP40 on the modular enclosure.