Schneider Electric A9DC8610 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9DC8610 Acti9 iCV40H RCBO, 10 A, C Curve

MPNA9DC8610
Active

Schneider Electric Acti9 iCV40H RCBO, 1P+N, 10 A, C curve, 10 kA Icn at 230 V AC, 300 mA earth-leakage sensitivity, clip-on DIN-rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Residual Current Protection

A9DC8610 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication Fault indication

Electrical Ratings

A9DC8610 — Electrical Ratings
ParameterValue
Rated current (In)10 A
Rated operational voltage (Ue)230 V AC 50/60 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability20000 cycles
Mechanical durability (operating cycles)20000 cycles

Identification

A9DC8610 — Identification
ParameterValue
Product nameActi9 iCV40
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiCV40H

Mechanical

A9DC8610 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminals top or bottom 1...16 mm² rigid Tunnel type terminals top or bottom 1...10 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width36 mm
Height85 mm
Depth73 mm

Environmental

A9DC8610 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity95 % at 55 °C
Operating altitude2000 m

Approvals

A9DC8610 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

The Schneider Electric A9DC8610 is an Acti9 iCV40H combined residual-current circuit breaker (RCBO) — one module wide, 1P+N, rated 10 A with a C curve. It integrates overcurrent protection (thermal-magnetic trip) and earth-leakage protection at 300 mA sensitivity into a single DIN-rail unit.

The 10 A rated current (In) sets the continuous load capacity; the C curve (magnetic trip 5–10 x In) tolerates moderate inrush from motor or lighting loads. The 300 mA earth-leakage threshold is for equipment protection, not personnel.

Clip-on mount to standard DIN rail. Neutral is on the left, phase on the right. Tunnel terminals accept 1–16 mm² rigid or 1–10 mm² flexible; strip 14 mm, torque to 2 N·m.

Listed as current production. The Acti9 range is Schneider's standard modular DIN-rail family; the iCV40H variant is a common RCBO for distribution outgoing circuits.

Frequently asked questions

What is the breaking capacity of the A9DC8610?

10,000 A Icn at 230 V AC, 50/60 Hz, conforming to EN/IEC 61009-2-1. That is the rated short-circuit breaking capacity for this RCBO.

What earth-leakage sensitivity does the A9DC8610 have?

300 mA — an equipment-protection threshold, not personnel protection. Suitable for circuits with higher expected ground-fault currents, like appliances or fixed machinery.

MPN
A9DC8610