Skip to main content
Schneider Electric A9DE3706 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9DE3706 Acti9 iCV40 6A 30mA RCBO, Curve

MPNA9DE3706
Active

Schneider Electric Acti9 iCV40 RCBO, A9DE3706, 3P+N, 6 A rated, 30 mA earth leakage, curve C, 6 kA breaking capacity at 400 V AC, thermal-magnetic trip, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9DE3706 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationFault indication ON/OFF indication
A9DE3706 — Electrical Ratings
ParameterValue
Rated current (In)6 A
Rated operational voltage (Ue)400 V AC 50/60 Hz
Poles description3P + N
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)440 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability20000 cycles
Mechanical durability (operating cycles)20000 cycles
A9DE3706 — Identification
ParameterValue
Product nameActi9 iCV40
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiCV40N
A9DE3706 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules10
Terminal connectionsTunnel type terminals top or bottom 1...16 mm² rigid Tunnel type terminals top or bottom 1...10 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width90 mm
Height93 mm
Depth73 mm
A9DE3706 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity95 % at 55 °C
Operating altitude2000 m
A9DE3706 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

The A9DE3706 is a 3P+N RCBO (residual current circuit breaker with overcurrent protection) from the Acti9 iCV40 series, combining a 6 A thermal-magnetic MCB with integrated 30 mA earth-leakage protection in a single DIN-rail module. The 6 A rated current and curve C (magnetic trip 5–10 × In) suit it for protecting final sub-circuits feeding resistive and light inductive loads — lighting, small appliances, control transformers — where the inrush is moderate and the steady draw stays under 6 A. The 30 mA sensitivity covers personnel protection against direct contact (30 mA is the standard threshold for shock protection per IEC 60364). Breaking capacity is 6 kA Icn at 400 V AC, 50/60 Hz, conforming to EN/IEC 61009-2-1. Limitation class 3 (energy-limiting) means the device clears a fault fast enough to restrict let-through energy, reducing stress on downstream wiring and loads. Rated for overvoltage category III (IEC 60364) and pollution degree 3, so it is suitable for fixed installations inside a distribution board where the environment is not climate-controlled but not directly exposed to rain or condensation. IP20 on the device body, IP40 inside the modular enclosure — fine for a clean, dry panel.

Clip-on mounting to DIN rail (35 mm symmetrical rail per EN 60715). The 3P+N unit occupies 10 modules of 9 mm pitch (90 mm total width), which is the standard footprint for a 3P+N RCBO in the Acti9 range. Neutral is on the left. Connection pitch is 18 mm between phases and 9 mm between phase and neutral — standard for busbar connection in Acti9 distribution boards. The 73 mm depth fits standard shallow enclosures; the toggle control provides local ON/OFF and fault indication visible through the enclosure door.

Frequently asked questions

What is the breaking capacity of A9DE3706?

The breaking capacity is 6 kA Icn at 400 V AC, 50/60 Hz, conforming to EN/IEC 61009-2-1.

What is the earth leakage sensitivity of A9DE3706?

The integrated earth-leakage protection is set at 30 mA sensitivity.

Where can I buy A9DE3706 and get current pricing?

The A9DE3706 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
A9DE3706