The Schneider Electric A9DE6620 is an Acti9 iCV40 RCBO — a combined overcurrent and residual-current device for final subcircuit protection. It carries a 20 A thermal-magnetic trip with C-curve characteristics and integrated 300 mA earth-leakage protection, all in a 1P+N format. The 4500 A breaking capacity at 230 V AC (EN/IEC 61009-2-1) is sized for domestic and light commercial distribution boards where the prospective fault current stays under that threshold.
Clip-on mounting to DIN rail (35 mm), occupying 4 x 9 mm pitches (36 mm wide). Neutral is on the left, phase on the right, with a 9 mm connection pitch between them. Tunnel terminals accept 1 to 16 mm² rigid or 1 to 10 mm² flexible cable; strip 14 mm and torque to 2 N·m.