Skip to main content
Schneider Electric A9DH3620 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9DH3620 Acti9 iCV40 20A 30mA RCBO, 6kA

MPNA9DH3620
Active

Schneider Electric Acti9 iCV40 RCBO, A9DH3620, 20 A, 30 mA earth leakage, B-curve, 6 kA, 1P+N, DIN rail.

$269.90Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9DH3620 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication Fault indication
A9DH3620 — Electrical Ratings
ParameterValue
Rated current (In)20 A
Rated operational voltage (Ue)230 V AC 50/60 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability20000 cycles
Mechanical durability (operating cycles)20000 cycles
A9DH3620 — Identification
ParameterValue
Product nameActi9 iCV40
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiCV40N
A9DH3620 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminals top or bottom 1...16 mm² rigid Tunnel type terminals top or bottom 1...10 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width36 mm
Height85 mm
Depth73 mm
A9DH3620 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity95 % at 55 °C
Operating altitude2000 m
A9DH3620 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

The Schneider Electric A9DH3620 is an Acti9 iCV40 residual-current circuit breaker with overcurrent protection (RCBO) — a single module that combines a 20 A thermal-magnetic MCB with a 30 mA earth-leakage detector in a 1P+N package.

Rated 20 A continuous and 6 kA breaking capacity (Icn) at 230 V AC, 50/60 Hz per EN/IEC 61009-2-1 — that 6 kA figure is the short-circuit it can safely interrupt under standard test conditions. For a domestic or light commercial final subcircuit fed by a transformer or a utility service with a prospective fault current under 6 kA, this RCBO covers the branch without needing an upstream current-limiting device. The 30 mA earth-leakage threshold meets the touch-protection requirement for socket-outlet circuits in most IEC-based wiring rules. Thermal-magnetic trip technology means the bimetal handles overloads (slow response to sustained overcurrent) while the solenoid handles short-circuits (instantaneous above the magnetic threshold).

Tunnel terminals top and bottom accept 1 to 16 mm² rigid or 1 to 10 mm² flexible cable; strip 14 mm and torque to 2 N·m. The 9 mm phase-to-neutral pitch keeps the busbar alignment clean in a multi-pole assembly.

Listed as current production (active lifecycle). This RCBO is a standard catalogue item in the Acti9 range.

Frequently asked questions

What is the earth-leakage sensitivity of this RCBO?

30 mA, integrated into the same unit as the overcurrent protection.

What compliance documentation does Schneider provide for the A9DH3620?

The RCBO carries EAC quality label and is designed to EN/IEC 61009-2-1. For RoHS, REACH, or UL declarations, refer to the manufacturer's compliance portal — those documents are not in this listing.

MPN