Panel-builder commissioning notes
The Schneider Electric A9DH3625 is an Acti9 iCV40 RCBO — a combined overcurrent and residual-current device rated 25 A, curve B, with 30 mA earth-leakage sensitivity and 6 kA breaking capacity at 230 V AC. The thermal-magnetic trip unit handles overload and short-circuit; the integrated earth-leakage block covers personnel protection at 30 mA.
Integration checklist
Tunnel terminals accept 1–16 mm² rigid or 1–10 mm² flexible; strip length 14 mm; tighten to 2 N·m. Connection pitch 9 mm between phase and neutral. Toggle control with ON/OFF and fault indication.