Schneider Electric A9DH3632 — Residual Current Breakers (RCCB/RCBO)

A9DH3632 Acti9 iCV40 32A 30mA RCBO, 6kA, B-Curve

MPNA9DH3632
Active

Schneider Electric Acti9 iCV40 RCBO, A9DH3632, 32 A, 30 mA, B-curve, 6 kA, 1P+N, DIN rail.

$274.85Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9DH3632 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication Fault indication
A9DH3632 — Electrical Ratings
ParameterValue
Rated current (In)32 A
Rated operational voltage (Ue)230 V AC 50/60 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability10000 cycles
Mechanical durability (operating cycles)20000 cycles
A9DH3632 — Identification
ParameterValue
Product nameActi9 iCV40
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiCV40N
A9DH3632 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminals top or bottom 1...16 mm² rigid Tunnel type terminals top or bottom 1...10 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width36 mm
Height85 mm
Depth73 mm
A9DH3632 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity95 % at 55 °C
Operating altitude2000 m
A9DH3632 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

Active-production RCBO for distribution outgoers

The A9DH3632 is a Schneider Electric Acti9 iCV40 residual-current circuit breaker with overcurrent protection (RCBO), combining a 32 A thermal-magnetic trip unit with integrated 30 mA earth-leakage protection in a single 1P+N module. Rated breaking capacity is 6 kA Icn at 230 V AC, 50/60 Hz, per EN/IEC 61009-2-1 — adequate for most residential and light commercial outgoer circuits where the prospective short-circuit current stays under that threshold. The B-curve (magnetic trip 3–5 x In) suits resistive and general-purpose loads where nuisance tripping from inrush is not a concern. The IP20 body (IP40 in modular enclosure) confirms it is designed for dry, enclosed panels only.

Lifecycle and compliance posture

EAC marking and EN/IEC 61009-2-1 conformance are documented. The part does not carry a UL listing on its spec sheet.

The 73 mm depth fits standard Acti9 enclosures without protruding beyond the door. Mechanical durability is rated at 20,000 cycles, electrical at 10,000 cycles — figures typical for a distribution-grade RCBO. For an MRO planner stocking spares, this is a long-life component in normal service; replacement intervals are driven by fault events, not wear-out.

Frequently asked questions

What is A9DH3632's listed depth?

The A9DH3632 has a depth of 73 mm, which fits standard Acti9 enclosures.

What is A9DH3632's listed range?

The A9DH3632 belongs to the Schneider Electric Acti9 range, specifically the iCV40 series.

MPN
A9DH3632