Active-production RCBO for distribution outgoers
The A9DH3632 is a Schneider Electric Acti9 iCV40 residual-current circuit breaker with overcurrent protection (RCBO), combining a 32 A thermal-magnetic trip unit with integrated 30 mA earth-leakage protection in a single 1P+N module. Rated breaking capacity is 6 kA Icn at 230 V AC, 50/60 Hz, per EN/IEC 61009-2-1 — adequate for most residential and light commercial outgoer circuits where the prospective short-circuit current stays under that threshold. The B-curve (magnetic trip 3–5 x In) suits resistive and general-purpose loads where nuisance tripping from inrush is not a concern. The IP20 body (IP40 in modular enclosure) confirms it is designed for dry, enclosed panels only.
Lifecycle and compliance posture
EAC marking and EN/IEC 61009-2-1 conformance are documented. The part does not carry a UL listing on its spec sheet.
The 73 mm depth fits standard Acti9 enclosures without protruding beyond the door. Mechanical durability is rated at 20,000 cycles, electrical at 10,000 cycles — figures typical for a distribution-grade RCBO. For an MRO planner stocking spares, this is a long-life component in normal service; replacement intervals are driven by fault events, not wear-out.