Skip to main content
Schneider Electric A9F04763 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F04763 Acti9 iC60 MCB, 63 A, 3P+N, C-Cu

MPNA9F04763
Active

Schneider Electric Acti9 iC60, miniature circuit breaker, 63 A, 3P+N, C-curve, 36 kA breaking capacity at 133 V AC, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F04763 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F04763 — Ratings
ParameterValue
Rated current (In)63 A
Poles configuration3P + N
Number of protected poles3
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F04763 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F04763 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches8

Environmental

A9F04763 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F04763 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The A9F04763 is a 63 A, 3P+N miniature circuit breaker from the Schneider Acti9 iC60 series, with a C-curve trip characteristic (magnetic trip at 8 x In ±20 %). The breaking capacity tells the real story: 36 kA Icu at 12–133 V AC, 20 kA at 220–240 V, 10 kA at 380–415 V, and 6 kA at 440 V AC per EN/IEC 60947-2. For IEC 60898-1 applications it's rated 6000 A Icn at 400 V. That means it can clear high fault currents on the low-voltage side of a distribution transformer without welding contacts — critical for a mill feeder or sub-distribution panel where available fault current can hit those levels.

Snaps onto a DIN rail (9 mm pitch, 8 pitches wide — 72 mm width, 91 mm height, 78.5 mm depth). The double terminals accept 1–35 mm² rigid or 1–25 mm² flexible; tightening torque is 3.5 N·m. IP20 rated, so it's for inside a panel — not washdown. The toggle provides local on/off with a trip indicator. Neutral on the left, 3 protected poles on the right. Earth-leakage protection requires a separate block (not built in).

Dual-certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (household/similar) — so it fits both a factory distribution board and a commercial sub-panel. Suitability for isolation is confirmed under both standards. Pollution degree 3, overvoltage category IV, tropicalisation class 2 per IEC 60068-1. 10,000 electrical cycles, 20,000 mechanical cycles.

Frequently asked questions

Where can I buy A9F04763 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at that time.

What is the A9F04763's breaking capacity at 400 V?

Under EN/IEC 60898-1 it is rated 6000 A Icn at 400 V AC; under EN/IEC 60947-2 it is rated 10 kA Icu at 380–415 V AC and 6 kA Icu at 440 V AC.

What compliance documentation does Schneider provide for A9F04763?

The breaker is certified to EN/IEC 60947-2 and EN/IEC 60898-1, with tropicalisation class 2 per IEC 60068-1. For RoHS, REACH, and UL documentation, check the manufacturer's product compliance portal or request a certificate of conformity with your order.

MPN
A9F04763