Schneider Electric A9F05303 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F05303 Acti9 iC60N MCB, 3A D Curve, 3P

MPNA9F05303
Obsolete

Schneider Electric Acti9 iC60N, miniature circuit breaker, 3 A, D curve, 3P, 50 kA Icu at 415 V AC, DIN rail, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F05303 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9F05303 — Ratings
ParameterValue
Rated current (In)3 A
Poles configuration3P
Number of protected poles3
Breaking capacity50 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)50 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV
A9F05303 — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles
A9F05303 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width54 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches6
A9F05303 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9F05303 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The A9F05303 is a Schneider Electric Acti9 iC60N miniature circuit breaker rated 3 A with a D curve, meaning the magnetic trip threshold is 12 x In ±20 % — so it holds through motor inrush without nuisance tripping, then clears hard faults fast. The 50 kA Icu at 415 V AC (per EN/IEC 60947-2) gives headroom for high-fault panels; the same unit also carries a 6 kA Icn at 400 V under EN/IEC 60898-1 for residential or light commercial coordination. Three poles, thermal-magnetic trip, overvoltage category IV — sized for distribution boards where the upstream transformer is close. Snaps onto a DIN rail (6 x 9 mm pitches), 54 mm wide, 91 mm tall, 78.5 mm deep. Double terminals top and bottom accept 1–25 mm² rigid or 1–16 mm² flexible; wire strip length 14 mm, torque to 2 N·m.

D-curve selectivity and the so-what

The D curve (12 x In magnetic trip) is the key differentiator from a C curve (5–10 x In) or B curve (3–5 x In). For a 3 A MCB, that means the magnetic release fires between 28.8 A and 43.2 A — high enough to pass the starting surge of a small motor or transformer, low enough to protect the downstream cable. If your BOM calls for a D-curve 3 A MCB, swapping in a C curve risks nuisance trips on every start; swapping in a B curve risks the same plus inadequate short-circuit protection for the load.

Dual-certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (residential/ commercial). Pollution degree 3, suitability for isolation marked on both standards. Separate earth-leakage block available if needed.

Frequently asked questions

What is the breaking capacity of A9F05303?

50 kA Icu at 415 V AC per EN/IEC 60947-2, and 6 kA Icn at 400 V per EN/IEC 60898-1. The full voltage-dependent table: 50 kA at 12–133 V, 50 kA at 220–240 V, 50 kA at 380–415 V, 25 kA at 440 V, and 10 kA at 6000 A Icn at 400 V.

Where can I buy A9F05303 and get current pricing?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial response.

What standards does A9F05303 comply with?

Certified to EN/IEC 60947-2 and EN/IEC 60898-1. Pollution degree 3, overvoltage category IV, tropicalisation class 2, limitation class 3. Suitable for isolation per both standards.

MPN