Skip to main content
Schneider Electric A9F05304 — Miniature Circuit Breakers (MCB)

A9F05304 Acti9 iC60N MCB, 4 A D Curve, 3P, 50 kA

MPNA9F05304
Obsolete

Schneider Electric Acti9 iC60N, A9F05304, miniature circuit breaker, 4 A rated current, D curve, 3-pole, 50 kA breaking capacity at 400 V AC, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F05304 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9F05304 — Ratings
ParameterValue
Rated current (In)4 A
Poles configuration3P
Number of protected poles3
Breaking capacity50 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)50 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV
A9F05304 — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles
A9F05304 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width54 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches6
A9F05304 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9F05304 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The A9F05304 is a Schneider Electric Acti9 iC60N miniature circuit breaker rated 4 A with a D tripping curve, 3 poles, and a 50 kA breaking capacity at 400 V AC.

At 440 V AC the Icu drops to 25 kA, and under the 60898-1 standard the Icn is 10 kA at 400 V AC. That 10 kA Icn is the figure for domestic/commercial final circuits; the 50 kA Icu is what matters for industrial coordination studies.

Snaps onto standard DIN rail (mounting support: DIN rail). The 3-pole body occupies 6 x 9 mm pitches (54 mm wide), so it fills three module spaces in a distribution board.

Frequently asked questions

Where can I buy the A9F05304 and get a price?

The A9F05304 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the D curve on the A9F05304 used for?

The D curve has a magnetic tripping threshold of 12 x In ±20%, designed for loads with high inrush current such as small motors, transformers, and discharge lighting where a B or C curve would cause nuisance tripping on startup.

What compliance documentation does the A9F05304 carry?

The A9F05304 is dual-certified to EN/IEC 60947-2 and EN/IEC 60898-1, and carries IP20 finger-safe protection (IEC 60529). It is suitable for isolation per both standards. Tropicalisation class 2 per IEC 60068-1 is also listed.

MPN
A9F05304