Overview
The A9F45206 is a Schneider Acti9 iC60 miniature circuit breaker with 2 poles, rated 6 A on a D-curve, and a breaking capacity of 36 kA per IEC 60947-2. This part is in active production.

Schneider Acti9 iC60 miniature circuit breaker, order code A9F45206, 2-pole, 6 A, D-curve, 36 kA breaking capacity, 133 V AC/DC, clip-on mount, IP20.
| Parameter | Value |
|---|---|
| Control type | Toggle |
| Network type | AC/DC |
| Product or component type | Miniature circuit-breaker |
| Voltage | 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| [Ue] rated operational voltage | 12...133 V AC 50/60 Hz 220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 440 V AC 50/60 Hz <= 125 V DC |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to EN/IEC 60947-2 |
| Breaking capacity | 36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 |
| Current | 6 A |
| [Ics] rated service breaking capacity | 27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC |
| Network frequency | 50/60 Hz |
| Poles description | 2P |
| Number of protected poles | 2 |
| Parameter | Value |
|---|---|
| Utilisation category | Category A conforming to EN/IEC 60947-2 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Mounting mode | Clip-on |
| Mounting support | Rail |
| Wire stripping length | 14 mm for top or bottom connection |
| Connections - terminals | Single terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible |
| Pollution degree | 3 conforming to EN/IEC 60947-2 |
| Relative humidity | 95 % at 55 °C |
| Depth | 78.5 mm |
| Width | 36 mm |
| Color | White |
| Height | 85 mm |
| Electrical durability | 10000 cycles |
| Mechanical durability | 20000 cycles |
| Standards | EN/IEC 60947-2 EN/IEC 60898-1 |
| Range | Acti9 |
| Curve code | D |
| 9 mm pitches | 4 |
| Tropicalisation | 2 conforming to IEC 60068-1 |
| Limitation class | 3 conforming to EN/IEC 60898-1 |
| Local signalling | Trip indicator |
| Device short name | IC60N |
| Tightening torque | 2 N.m top or bottom |
| Overvoltage category | IV |
| Trip unit technology | Thermal-magnetic |
| Magnetic tripping limit | 12 x In +/- 20 % |
| Earth-leakage protection | Separate block |
| Provision for padlocking | Padlockable |
| Contact position indicator | Yes |
| Ambient air temperature for storage | -40...85 °C |
| Ambient air temperature for operation | -35...70 °C |
The A9F45206 is a Schneider Acti9 iC60 miniature circuit breaker with 2 poles, rated 6 A on a D-curve, and a breaking capacity of 36 kA per IEC 60947-2. This part is in active production.