Skip to main content
Schneider Electric A9F64203

Schneider A9F64203 Acti 9 iC60 MCB, 2-pole, 3 A, C-curve

MPNA9F64203
Obsolete

Schneider Electric Acti 9 iC60 A9F64203 miniature circuit breaker, 2-pole, 3 A rated, C-curve, 10 kA breaking capacity (Icu) per IEC 60947-2, 6 kV impulse withstand, thermal-magnetic trip, toggle control, IP20, clip-on mounting.

$46.20Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F64203 key specifications
ParameterValue
Control typeToggle
Network typeAC
Product or component typeMiniature circuit-breaker
Voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Ue] rated operational voltage220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2
Breaking capacity10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 4500 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Current3 A
[Ics] rated service breaking capacity10 kA 100 % x Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA 100 % x Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Network frequency50/60 Hz
Poles description2P
Number of protected poles2

All specifications

A9F64203 additional specifications
ParameterValue
Utilisation categoryCategory A conforming to EN/IEC 60947-2
IP degree of protectionIP20 conforming to IEC 60529 IP40 in modular enclosure (Insulation class II) conforming to IEC 60529
Mounting modeClip-on Removable comb busbar installed
Mounting support35 mm DIN rail
Connection pitch18 mm between phases
Wire stripping length14 mm for top or bottom connection
Connections - terminalsSingle terminal (top or bottom) , for 1 cable(s) , 1...25 mm², rigid, copper Single terminal (top or bottom) , for 1 cable(s) , 1...16 mm², flexible, copper Single terminal (top or bottom) , for 1 cable(s) , 1...16 mm², flexible with ferrule, copper Single terminal (top or bottom) , for 1.0 cable(s) , flexible, copper or aluminium, with ring terminal and accessory
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 %
Operating altitude0...2000 m
Width36 mm
ColorWhite
StandardsEN/IEC 60947-2 EN/IEC 60898-1
RangeActi9
Curve codeC
9 mm pitches4
Tropicalisation2 conforming to IEC 60068-1
Limitation class3 conforming to EN/IEC 60898-1
Local signallingTrip indicator
Device short nameiC60a
Tightening torque2 N.m top or bottom
Device applicationDistribution
Overvoltage categoryII
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Contact position indicatorYes
Ambient air temperature for storage-40...85 °C
Ambient air temperature for operation-35...70 °C

Product details

Overview

The A9F64203 is a Schneider Acti 9 iC60 miniature circuit breaker rated 3 A with a C-curve magnetic trip (8 x In +/- 20 %), switching 2 poles on a 220 V AC network at 50/60 Hz. It carries a 10 kA breaking capacity (Icu) per IEC 60947-2 and meets both EN/IEC 60947-2 and EN/IEC 60898-1, with a 6 kV impulse withstand voltage and suitability for isolation per both standards.

Compared to the 1-pole A9F74602 (50 kA Icu, 2 A), the A9F64203 offers 2 poles at 3 A with a 10 kA breaking capacity — choose the A9F74602 when the BOM requires a single-pole device with higher fault current headroom.

MPN
A9F64203