Skip to main content
Schneider Electric A9F87416

Schneider A9F87416 Acti9 iC60H MCB, 4-pole, 16 A, C-curve, 42 kA

MPNA9F87416
Obsolete

Schneider Acti9 iC60H miniature circuit breaker, order code A9F87416, 4-pole, 16 A, C-curve, 42 kA breaking capacity, 133 V AC/DC, thermal-magnetic trip, clip-on mounting, IP20.

$105.74Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F87416 key specifications
ParameterValue
Control typeToggle
Network typeAC DC
Product or component typeMiniature circuit-breaker
Voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Ue] rated operational voltage12...133 V AC 50/60 Hz 220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 440 V AC 50/60 Hz <= 250 V DC
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2
Breaking capacity42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Current16 A
[Ics] rated service breaking capacity21 kA 50 % x Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA 50 % x Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 7.5 kA 50 % x Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 5 kA 50 % x Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA 100 % x Icu at <= 250 V DC conforming to EN/IEC 60947-2
Network frequency50/60 Hz
Poles description4P
Number of protected poles4

All specifications

A9F87416 additional specifications
ParameterValue
Utilisation categoryCategory A conforming to EN/IEC 60947-2
IP degree of protectionIP20 conforming to IEC 60529 IP40 in modular enclosure (Insulation class II) conforming to IEC 60529
Mounting modeClip-on Removable comb busbar installed
Mounting support35 mm DIN rail
Connection pitch18 mm between phases
Wire stripping length14 mm for top or bottom connection
Connections - terminalsSingle terminal (top or bottom) , for 1 cable(s) , 1...25 mm², rigid, copper Single terminal (top or bottom) , for 1 cable(s) , 1...16 mm², flexible, copper Single terminal (top or bottom) , for 1 cable(s) , 1...16 mm², flexible with ferrule, copper Single terminal (top or bottom) , for 1.0 cable(s) , flexible, copper or aluminium, with ring terminal and accessory
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Operating altitude0...2000 m
Depth78.5 mm
Width72 mm
ColorWhite
Height85 mm
Product weight0.5 kg
Electrical durability10000 cycles
Mechanical durability20000 cycles
StandardsEN/IEC 60947-2 EN/IEC 60898-1
RangeActi9
Curve codeC
9 mm pitches8
Quality labelsNF
Tropicalisation2 conforming to IEC 60068-1
Limitation class3 conforming to EN/IEC 60898-1
Local signallingTrip indicator
Device short nameiC60H
Tightening torque2 N.m top or bottom
Device applicationDistribution
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1
Contact position indicatorYes
Ambient air temperature for storage-40...85 °C
Ambient air temperature for operation-35...70 °C
Comb busbar and distribution block compatibilityTop or bottom: YES

Product details

Overview

The A9F87416 is a Schneider Acti9 iC60H miniature circuit breaker with 4 poles, rated 16 A switching current, C-curve, and a breaking capacity of 42 kA per EN/IEC 60947-2. It operates on 133 V AC/DC and uses a thermal-magnetic trip unit. This part is in active production.

MPN