Specifications

A9K02713 key specifications
ParameterValue
Control typeToggle
Network typeAC
Product or component typeMiniature circuit-breaker
Voltage440 V AC 50/60 Hz
[Ue] rated operational voltage400 V AC 50/60 Hz
Breaking capacity6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Current13 A
[Ics] rated service breaking capacity6000 A 100 % x Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network frequency50/60 Hz
Poles description3P + N
Number of protected poles1
IP degree of protectionIP20 conforming to IEC 60529

All specifications

A9K02713 additional specifications
ParameterValue
Mounting modeFixed
Mounting supportDIN rail
Connection pitch18 mm between phases 18 mm between phase and neutral
Wire stripping length14 mm for top or bottom connection
Connections - terminalsTunnel type terminals (downstream) , 0.5...35 mm², rigid Tunnel type terminals (upstream) , 0.5...35 mm², rigid Tunnel type terminals (downstream) , 0.5...25 mm², flexible Tunnel type terminals (upstream) , 0.5...25 mm², flexible
Relative humidity95 % at 55 °C
Operating altitude0...2000 m
Depth70 mm
Width72 mm
ColorWhite
Height81 mm
Product weight0.48 kg
Electrical durability20000 cycles
Mechanical durability20000 cycles
StandardsEN/IEC 60898-1
RangeActi9
Curve codeC
9 mm pitches8
Tropicalisation2 conforming to IEC 60068-1
Limitation class3 conforming to EN/IEC 60898-1
Local signallingWithout
Neutral positionLeft
Device short nameK60N
Tightening torque3.5 N.m top or bottom
Device applicationDistribution
Overvoltage categoryII
Trip unit technologyThermal-magnetic
Magnetic tripping limit5...10 x In
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60898-1
Contact position indicatorNo
Ambient air temperature for storage-40...70 °C
Ambient air temperature for operation-25...70 °C
Comb busbar and distribution block compatibilityDownside: biconnect
MPN