Skip to main content
Schneider Electric A9KR11463BQ — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9KR11463BQ Acti9 ID K RCCB, 63 A, 30 mA,

MPNA9KR11463BQ
Active

Schneider Electric Acti9 ID K, residual current circuit breaker (RCCB), 4P, 63 A, 30 mA, 380-415 V AC, DIN rail clip-on, IP20/IP40.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9KR11463BQ — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
A9KR11463BQ — Electrical Ratings
ParameterValue
Rated current (In)63 A
Rated operational voltage (Ue)380...415 V AC 50 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)440 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemGroup incomer
Electrical durabilityAC-1: 4000 cycles
Mechanical durability (operating cycles)5000 cycles
A9KR11463BQ — Identification
ParameterValue
Product nameActi9 ID K
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameID K
A9KR11463BQ — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules8
Terminal connectionsBiconnect top or bottom 1...35 mm² rigid Biconnect top or bottom 1...25 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width72 mm
Height81 mm
Depth68 mm
A9KR11463BQ — Environmental
ParameterValue
Operating ambient temperature-5...55 °C
Storage ambient temperature-25...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree2
Relative humidity95 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9KR11463BQ — Approvals
ParameterValue
StandardsIS 12640-1 EN/IEC 61008-1 EN/IEC 61008-2-1

Product details

The Schneider Electric A9KR11463BQ is a 4-pole residual current circuit breaker (RCCB) from the Acti9 ID K series, rated 63 A continuous current with 30 mA earth-leakage sensitivity.

The 30 mA sensitivity is instantaneous (no time delay), so it trips on the first half-cycle of a ground fault — this is the standard for personnel protection in IEC 61008-1 circuits. The insulation voltage (Ui) is 440 V AC, so the internal clearances and creepage are sized for a 440 V system even though the operational voltage is capped at 415 V. That headroom matters when the supply rides high or when the RCCB is used in a corner-grounded delta configuration (rare, but the rating covers it).

Terminals accept rigid conductors up to 35 mm² or flexible up to 25 mm², with a stripping length of 14 mm and tightening torque of 3.5 N.m. The biconnect design allows top or bottom feed — useful when daisy-chaining through the same terminal without a separate busbar. IP20 on the body, IP40 inside a modular enclosure, so it needs a cabinet or distribution board to meet washdown or dust ingress requirements.

The Acti9 ID K family is a standard line, not a niche or phased-out variant.

The A9KR11463BQ is certified to IS 12640-1, EN/IEC 61008-1, and EN/IEC 61008-2-1. That covers the Indian standard and the European harmonized standard for residual current operated circuit-breakers without integral overcurrent protection. Pollution degree 2 (non-conductive pollution that becomes conductive only when condensation occurs) is the typical rating for enclosed distribution boards.

Frequently asked questions

Where can I buy A9KR11463BQ and what is the lead time?

The A9KR11463BQ is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the closest alternative to A9KR11463BQ in the same family?

The A9KR11463BQ is a standard Acti9 ID K RCCB. Within the same family, other order codes differ by rated current and sensitivity; no pin-compatible direct replacement is listed as an official successor.

What is A9KR11463BQ's depth?

The depth is 68 mm.

What compliance documentation does Schneider provide for A9KR11463BQ?

The device is certified to IS 12640-1, EN/IEC 61008-1, and EN/IEC 61008-2-1. It also meets tropicalization class 2 per IEC 60068-1 and pollution degree 2.

MPN