Skip to main content
Schneider Electric A9KS15363BQ — Circuit Breaker Accessories

Schneider Electric A9KS15363BQ Acti9 SW 3P 63A Switch Discon

MPNA9KS15363BQ
Obsolete

Schneider Electric Acti9 SW, switch disconnector, 3P, 63 A at 415 V AC, AC-22A, IEC 60947-3, DIN rail, set of 4, white.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9KS15363BQ — Identification
ParameterValue
Product / component typeSwitch disconnector
Product nameActi9 SW
Product rangeActi9
Device applicationControl
A9KS15363BQ — Electrical
ParameterValue
Rated operational voltage [Ue]415 V AC 50/60 Hz
Rated insulation voltage [Ui]500 V AC 50/60 Hz
Rated impulse withstand voltage [Uimp]4 kV conforming to IEC 60947-3
Poles description3P
A9KS15363BQ — Protection & Performance
ParameterValue
Utilisation categoryAC-22A
Mechanical durability20000 cycles
Electrical durability10000 cycles
A9KS15363BQ — Mechanical
ParameterValue
Connections / terminalsTunnel type terminals (downstream) - 1...35 mm² - rigid Tunnel type terminals (downstream) - 1...25 mm² - flexible Tunnel type terminals (upstream) - 1...35 mm² - rigid Tunnel type terminals (upstream) - 1...25 mm² - flexible
Device short nameSW
Control typeToggle
Mounting modeFixed
Mounting supportDIN rail
Usable 9 mm pitches6
Width54 mm
Height81 mm
Depth68.5 mm
ColourWhite
A9KS15363BQ — Environmental
ParameterValue
IP degree of protectionIP20
Pollution degree2
Operating ambient air temperature-5...55 °C
Storage ambient air temperature-25...85 °C
A9KS15363BQ — Approvals
ParameterValue
StandardsIEC 60947-3

Product details

The A9KS15363BQ is a Schneider Electric Acti9 SW switch disconnector — 3 poles, rated 63 A at 415 V AC in AC-22A utilisation category, per IEC 60947-3. That AC-22A rating means it's designed for switching mixed resistive and inductive loads, including motor circuits with moderate inrush, not just pure resistive heating. It comes as a set of 4 units, each with a toggle control, tunnel terminals accepting up to 35 mm² rigid, and IP20 finger-safe enclosure for panel mounting.

Panel Integration

Each unit takes 6 x 9 mm pitches of rail width — 54 mm per pole count, so the 3-pole assembly occupies 54 mm. Tunnel terminals accept 1…35 mm² rigid or 1…25 mm² flexible, with a 9 mm strip length and 3.5 N·m tightening torque. Operating temperature range is -5…55 °C, storage -25…85 °C, with 95% humidity tolerance at 55 °C (tropicalisation class 2).

Frequently asked questions

Where can I buy A9KS15363BQ?

This obsolete part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time figure is carried here.

What is the A9KS15363BQ rated for?

It is a 3-pole switch disconnector rated 63 A at 415 V AC in AC-22A utilisation category, with a short-time withstand of 756 A for 300 ms and impulse withstand of 4 kV, all per IEC 60947-3.

MPN
A9KS15363BQ