Three poles protected, thermal-magnetic trip, and it carries both EN/IEC 60898-1 and EN/IEC 60947-2 certifications, meaning it's rated for both household-style and industrial branch-circuit duty.
The D curve means the magnetic trip fires at 10 to 14 times rated current — 100 to 140 A for this 10 A breaker. The 6 kA Icn (per EN/IEC 60898-1) is the service breaking capacity for general distribution; the 10 kA Icu (per IEC 60947-2) is the ultimate breaking capacity for industrial panels, so this breaker can interrupt a fault up to 10 kA at 400 V AC without failing.
Integration notes
Tunnel-type terminals accept 0.33 to 10 mm² flexible or 0.75 to 16 mm² rigid wire; strip length 13 mm, tighten to 2 N.m. The toggle gives local ON/OFF indication. If you need earth-leakage protection, a separate residual-current block can be added downstream.