Skip to main content
Schneider Electric A9N21399 — Miniature Circuit Breakers (MCB)

Schneider Electric A9N21399 DT40 MCB, 32 A, 3P, Curve D, 6 k

MPNA9N21399
Obsolete

Schneider Electric ProDis DT40 miniature circuit-breaker, A9N21399, 32 A, 3P, curve D, 6 kA Icn / 10 kA Icu, clip-on DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N21399 — Identification
ParameterValue
Product nameDT40
Product rangeProdis
Product range (series)ProDis
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9N21399 — Ratings
ParameterValue
Rated current (In)32 A
Poles configuration3P
Number of protected poles3
Breaking capacity6000 A Icn at 400 V AC 50 Hz conforming to EN/IEC 60898-1 10 kA Icu at 400...415 V AC 50 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)6000 A 100 % x Icn at 400 V AC 50 Hz conforming to EN/IEC 60898-1 7.5 kA 75 % x Icu at 400 V AC 50 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)400 V AC 50 Hz between phases
Rated insulation voltage (Ui)440 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50 Hz
A9N21399 — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit10...14 x In
Earth-leakage protectionSeparate block
Suitability for isolationYes
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles
A9N21399 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Terminal connection typeTunnel type terminals downstream 0.33...10 mm² flexible Tunnel type terminals downstream 0.75...16 mm² rigid Tunnel type terminals upstream 0.33...10 mm² flexible Tunnel type terminals upstream 0.75...16 mm² rigid
Terminal tightening torque2 N.m
Wire stripping length13 mm
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Width54 mm
Height81 mm
Depth78 mm
Number of 9 mm pitches6
A9N21399 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...70 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9N21399 — Approvals
ParameterValue
StandardsEN/IEC 60898-1 EN/IEC 60947-2

Product details

The Schneider Electric A9N21399 is a DT40 miniature circuit-breaker from the ProDis range, rated 32 A with 3 protected poles and a D tripping curve. The D curve means magnetic trip occurs at 10 to 14 times the rated current (10–14 x In), so it handles high inrush loads like motor starters and small transformers without nuisance tripping — that is the main reason to pick D over B or C in a distribution board feeding inductive equipment. Breaking capacity is 6000 A Icn at 400 V AC per EN/IEC 60898-1, and 10 kA Icu at 400–415 V AC per IEC 60947-2. The 78 mm depth and 81 mm height leave clearance for standard enclosure depths.

Clip-on DIN rail mount means it snaps directly into a 35 mm rail inside a distribution board or control panel. IP20 finger protection (IEC 60529) is standard for enclosed panels — no special sealing needed.

Frequently asked questions

Where can I buy the A9N21399 and get a price?

The A9N21399 is sourced to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

What is the breaking capacity of the A9N21399?

The A9N21399 has a breaking capacity of 6000 A Icn at 400 V AC per EN/IEC 60898-1, and 10 kA Icu at 400–415 V AC per IEC 60947-2. The 10 kA Icu rating is the industrial fault-interruption figure.

What does the D curve mean on this MCB?

The D curve means magnetic tripping occurs at 10 to 14 times the rated current (10–14 x In). This is designed for loads with high inrush current, such as motor starters, small transformers, and welding equipment — it avoids nuisance trips that a B or C curve would cause on those loads.

MPN
A9N21399