It clips onto DIN rail and is built for distribution applications in residential and commercial panels. Breaking capacity is dual-rated: 6000 A Icn at 400 V AC per EN/IEC 60898-1 for general distribution, and 10 kA Icu at 400–415 V AC per IEC 60947-2 for industrial coordination. That 10 kA rating gives headroom in sub-distribution boards where fault levels are higher than a standard domestic board.
Clip-on mounting to DIN rail (35 mm per EN 60715) — no tools needed for rail attachment. The 3P+N occupies 6 module pitches (9 mm each), so it takes 54 mm of rail width. IP20 finger-safe terminals allow panel wiring without additional shrouding.
Compliance covers both the wiring-rule standard (EN/IEC 60898-1) and the industrial standard (EN/IEC 60947-2), so the breaker qualifies for installations where the local code requires either. Operating altitude is limited to 2000 m without derating. Earth-leakage protection requires a separate block (not integrated). The neutral pole is left-positioned, and the toggle provides local ON/OFF indication.