Breaking capacity is 6 kA Icn at 400 V AC per EN/IEC 60898-1, and 10 kA Icu at 400–415 V AC per IEC 60947-2 — the dual standard means it qualifies for both residential and industrial coordination studies.
Curve C (magnetic tripping limit 5–10 × In) means the breaker tolerates moderate inrush currents — suitable for general-purpose distribution feeding lighting banks, small motor starters, and control transformers where the startup surge stays under 320 A peak. The neutral position is left, matching the typical busbar layout in Schneider distribution boards.