Breaking capacity is dual-rated: 6 kA Icn per EN/IEC 60898-1 for general distribution, and 10 kA Icu per IEC 60947-2 for industrial panel duty. Clip-on mounting to DIN rail, 54 mm wide (6 x 9 mm pitches), with tunnel terminals accepting up to 16 mm² rigid or 10 mm² flexible on both line and load sides. IP20 finger-safe front; the 78 mm depth leaves clearance behind a standard 100 mm deep enclosure gland plate.
Dual-standard certification and deployment context
Rated to both EN/IEC 60898-1 (household / similar installation MCB standard) and EN/IEC 60947-2 (industrial low-voltage switchgear standard). This dual rating is the key spec for a panel builder: the 60898-1 side covers the branch circuit protection for a fixed load, while the 60947-2 side covers the isolation and fault-breaking duty inside an industrial enclosure. The 2000 m operating altitude covers most industrial sites; above that, dielectric strength derates per the standard.
D curve selection — what it means for the buyer