The Schneider Electric A9N3P02CGN is an Acti9 xC60 miniature circuit breaker rated 2 A with a C-curve magnetic trip (5 to 10 x In) and 3 protected poles (3P). It clips onto a 35 mm DIN rail for panel integration and carries a 10 kA Icn breaking capacity at both 240 V and 415 V AC, certified to IS/IEC 60898-1.
The C-curve means the magnetic trip fires between 5 and 10 times In (10 to 20 A), so it tolerates moderate inrush from capacitive or lightly inductive loads without nuisance tripping. The 10 kA Icn at 240 V and 415 V AC is the maximum prospective fault current the breaker can safely interrupt; this matches typical domestic and commercial supply capacities in IEC markets. The 3-pole version (3P) switches all three phases simultaneously, suitable for three-phase distribution sub-circuits.
Panel integration and installation
Clip-on mounting to a 35 mm DIN rail, occupying 6 x 9 mm pitches (54 mm width). Tunnel-type terminals accept up to 25 mm² rigid or 16 mm² flexible conductors; strip length 13 mm. Tightening torque 2 N·m.