Schneider Electric A9N3P03CIN — Miniature Circuit Breakers (MCB)

Schneider Electric A9N3P03CIN Acti9 xC60 MCB, 3 A C-Curve, 1

MPNA9N3P03CIN
Active

Schneider Electric Acti9 xC60 miniature circuit breaker, A9N3P03CIN, 3 A rated current, C-curve, 10 kA breaking capacity at 415 V AC, 3-pole, clip-on DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N3P03CIN — Identification
ParameterValue
Product nameXC60
Product rangeActi9
Product range (series)Acti9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9N3P03CIN — Ratings
ParameterValue
Rated current (In)3 A
Poles configuration3P
Number of protected poles3
Breaking capacity10 kA Inc at 380...415 V AC 50/60 Hz conforming to IS/IEC 60947-2 15 kA Icu at 100...125 V DC conforming to IS/IEC 60947-2
Rated service breaking capacity (Ics)7.5 kA conforming to IS/IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA conforming to IS/IEC 60947-2 - 100...125 V DC
Rated operational voltage (Ue)220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 100...125 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to IS/IEC 60947-2
Rated impulse withstand voltage (Uimp)4 kV conforming to IS/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to IS/IEC 60947-2
Overvoltage categoryIV
A9N3P03CIN — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to IS/IEC 60947-2
Limitation class3 conforming to IS/IEC 60947-2
Electrical durability (cycles)20000 cycles
Mechanical durability (cycles)20000 cycles
A9N3P03CIN — Mechanical
ParameterValue
Mounting support35 mm DIN rail
Mounting modeClip-on
Control typeToggle
Terminal connection typeTunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)
Terminal tightening torque2 N.m
Wire stripping length13 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Width54 mm
Height85 mm
Depth77.5 mm
Number of 9 mm pitches6
A9N3P03CIN — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Pollution degree3
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9N3P03CIN — Approvals
ParameterValue
StandardsIS/IEC 60947-2

Product details

The A9N3P03CIN is a 3-pole miniature circuit breaker from the Schneider Electric Acti9 xC60 series, rated 3 A with a C-curve trip characteristic. The 10 kA breaking capacity at 380–415 V AC (IS/IEC 60947-2) tells you it can safely interrupt a fault current up to 10 kA at that voltage — enough for most commercial and light industrial distribution boards. The 15 kA Icu at 100–125 V DC extends its use into DC circuits, though the AC rating is the primary spec for panel builders. The 54 mm width for three poles is compact — six 9 mm pitches per the spec — so it fits tightly in a crowded DIN rail assembly. IP20 finger protection is standard for enclosed distribution boards; no washdown rating here, so keep it behind a panel door.

The suitability-for-isolation marking confirms it can be used as a disconnecting means per IS/IEC 60947-2. Compliance documentation (RoHS, REACH, UL) is typically available from Schneider's product certification portal; the evidence does not list specific certs beyond the IEC standard.

Frequently asked questions

Where can I buy A9N3P03CIN and how do I get a price?

The A9N3P03CIN is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is A9N3P03CIN's listed depth (77.5 mm) on this component line?

The depth is 77.5 mm, which is standard for the Acti9 xC60 range and fits within typical 100 mm deep enclosures.

What is A9N3P03CIN's listed range (Acti9) on this component line?

The range is Acti9, Schneider Electric's modular DIN-rail miniature circuit breaker family for distribution and final-circuit protection.

MPN