Schneider Electric A9N3P03DIN — Miniature Circuit Breakers (MCB)

Schneider Electric A9N3P03DIN Acti9 xC60 MCB, 3 A D Curve, 1

MPNA9N3P03DIN
Active

Schneider Electric Acti9 xC60 miniature circuit breaker, A9N3P03DIN, 3 A rated current, D curve, 10 kA breaking capacity at 415 V AC, 3-pole, clip-on 35 mm DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N3P03DIN — Identification
ParameterValue
Product nameXC60
Product rangeActi9
Product range (series)Acti9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9N3P03DIN — Ratings
ParameterValue
Rated current (In)3 A
Poles configuration3P
Number of protected poles3
Breaking capacity10 kA Inc at 380...415 V AC 50/60 Hz conforming to IS/IEC 60947-2 15 kA Icu at 100...125 V DC conforming to IS/IEC 60947-2
Rated service breaking capacity (Ics)7.5 kA conforming to IS/IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA conforming to IS/IEC 60947-2 - 100...125 V DC
Rated operational voltage (Ue)220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 100...125 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to IS/IEC 60947-2
Rated impulse withstand voltage (Uimp)4 kV conforming to IS/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to IS/IEC 60947-2
Overvoltage categoryIV
A9N3P03DIN — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to IS/IEC 60947-2
Limitation class3 conforming to IS/IEC 60947-2
Electrical durability (cycles)20000 cycles
Mechanical durability (cycles)20000 cycles
A9N3P03DIN — Mechanical
ParameterValue
Mounting support35 mm DIN rail
Mounting modeClip-on
Control typeToggle
Terminal connection typeTunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)
Terminal tightening torque2 N.m
Wire stripping length13 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Width54 mm
Height85 mm
Depth77.5 mm
Number of 9 mm pitches6
A9N3P03DIN — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Pollution degree3
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9N3P03DIN — Approvals
ParameterValue
StandardsIS/IEC 60947-2

Product details

Panel fit and protection profile

The Schneider Electric A9N3P03DIN is a 3-pole Acti9 xC60 miniature circuit breaker rated at 3 A with a D tripping curve. The D curve means magnetic tripping occurs at 12 x In ±20 % — so it holds through the high inrush of motor or transformer loads without nuisance trips, then clears fast on a hard fault. Breaking capacity is 10 kA Icn at 380–415 V AC 50/60 Hz per IS/IEC 60947-2, and 15 kA Icu at 100–125 V DC. The thermal-magnetic trip unit protects the downstream cable and load. The suitability-for-isolation marking (yes, per IS/IEC 60947-2) means you can use it as a local disconnecting means for the downstream equipment.

Integration notes

IP20 finger-safe protection means it is intended for enclosure use, not open-panel washdown areas. Tropicalisation level 2 per IEC 60068-1 means the part is treated for storage and operation in warm, humid climates — relevant if the panel ships to Southeast Asia or coastal regions.

Frequently asked questions

What is the breaking capacity of A9N3P03DIN?

10 kA Icn at 380–415 V AC 50/60 Hz per IS/IEC 60947-2, and 15 kA Icu at 100–125 V DC.

What does the D curve mean on this breaker?

The D curve sets magnetic tripping at 12 x In ±20 %, so the breaker holds through high inrush currents from motors or transformers without nuisance tripping, then clears fast on a hard short-circuit.

What compliance standards does A9N3P03DIN meet?

The breaker is certified to IS/IEC 60947-2, with tropicalisation level 2 per IEC 60068-1 and pollution degree 3. It is suitable for isolation per the same standard.

MPN