Skip to main content
Schneider Electric A9N3P06CIN — Miniature Circuit Breakers (MCB)

Schneider Electric A9N3P06CIN Acti9 xC60 MCB, 6 A, C Curve,

MPNA9N3P06CIN
Active

Schneider Electric Acti9 xC60 miniature circuit-breaker, A9N3P06CIN, 6 A, C curve, 3 poles, 10 kA breaking capacity at 415 V AC, IS/IEC 60947-2.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N3P06CIN — Identification
ParameterValue
Product nameXC60
Product rangeActi9
Product range (series)Acti9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9N3P06CIN — Ratings
ParameterValue
Rated current (In)6 A
Poles configuration3P
Number of protected poles3
Breaking capacity10 kA Inc at 380...415 V AC 50/60 Hz conforming to IS/IEC 60947-2 15 kA Icu at 100...125 V DC conforming to IS/IEC 60947-2
Rated service breaking capacity (Ics)7.5 kA conforming to IS/IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA conforming to IS/IEC 60947-2 - 100...125 V DC
Rated operational voltage (Ue)220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 100...125 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to IS/IEC 60947-2
Rated impulse withstand voltage (Uimp)4 kV conforming to IS/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to IS/IEC 60947-2
Overvoltage categoryIV
A9N3P06CIN — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to IS/IEC 60947-2
Limitation class3 conforming to IS/IEC 60947-2
Electrical durability (cycles)20000 cycles
Mechanical durability (cycles)20000 cycles
A9N3P06CIN — Mechanical
ParameterValue
Mounting support35 mm DIN rail
Mounting modeClip-on
Control typeToggle
Terminal connection typeTunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)
Terminal tightening torque2 N.m
Wire stripping length13 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Width54 mm
Height85 mm
Depth77.5 mm
Number of 9 mm pitches6
A9N3P06CIN — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Pollution degree3
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9N3P06CIN — Approvals
ParameterValue
StandardsIS/IEC 60947-2

Product details

The Schneider Electric A9N3P06CIN is an Acti9 xC60 miniature circuit-breaker rated at 6 A with a C curve, 3 poles, and a breaking capacity of 10 kA Icn at 380–415 V AC and 15 kA Icu at 100–125 V DC, certified to IS/IEC 60947-2.

The 15 kA DC rating on the same pole stack is useful for DC auxiliary circuits or battery-backed loads. Thermal-magnetic trip technology means the bimetal handles overloads and the solenoid handles shorts — no electronics to fail or need configuration.

Frequently asked questions

What is the breaking capacity of the A9N3P06CIN?

The A9N3P06CIN has a breaking capacity of 10 kA Icn at 380–415 V AC 50/60 Hz and 15 kA Icu at 100–125 V DC, both conforming to IS/IEC 60947-2.

What standards does the A9N3P06CIN comply with?

It complies with IS/IEC 60947-2, which covers low-voltage switchgear and controlgear for circuit-breakers. It also meets tropicalisation class 2 per IEC 60068-1 and limitation class 3 per IS/IEC 60947-2.

How do I get pricing and availability for the A9N3P06CIN?

The A9N3P06CIN is sourced to order against an RFQ through independent distribution; submit a request for current pricing and confirmed availability.

MPN
A9N3P06CIN