Skip to main content
Schneider Electric A9N3P06DIN — Miniature Circuit Breakers (MCB)

Schneider Electric A9N3P06DIN Acti9 xC60 MCB, 6 A D Curve, 3

MPNA9N3P06DIN
Active

Schneider Electric Acti9 xC60, A9N3P06DIN, miniature circuit breaker, 3P, 6 A, D curve, 10 kA at 415 V AC, clip-on DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N3P06DIN — Identification
ParameterValue
Product nameXC60
Product rangeActi9
Product range (series)Acti9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9N3P06DIN — Ratings
ParameterValue
Rated current (In)6 A
Poles configuration3P
Number of protected poles3
Breaking capacity10 kA Inc at 380...415 V AC 50/60 Hz conforming to IS/IEC 60947-2 15 kA Icu at 100...125 V DC conforming to IS/IEC 60947-2
Rated service breaking capacity (Ics)7.5 kA conforming to IS/IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA conforming to IS/IEC 60947-2 - 100...125 V DC
Rated operational voltage (Ue)220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 100...125 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to IS/IEC 60947-2
Rated impulse withstand voltage (Uimp)4 kV conforming to IS/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to IS/IEC 60947-2
Overvoltage categoryIV
A9N3P06DIN — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to IS/IEC 60947-2
Limitation class3 conforming to IS/IEC 60947-2
Electrical durability (cycles)20000 cycles
Mechanical durability (cycles)20000 cycles
A9N3P06DIN — Mechanical
ParameterValue
Mounting support35 mm DIN rail
Mounting modeClip-on
Control typeToggle
Terminal connection typeTunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)
Terminal tightening torque2 N.m
Wire stripping length13 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Width54 mm
Height85 mm
Depth77.5 mm
Number of 9 mm pitches6
A9N3P06DIN — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Pollution degree3
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9N3P06DIN — Approvals
ParameterValue
StandardsIS/IEC 60947-2

Product details

Integrator's note on the A9N3P06DIN

The Schneider Electric A9N3P06DIN is a 3-pole Acti9 xC60 miniature circuit breaker rated 6 A with a D tripping curve. The thermal-magnetic trip unit triggers magnetically at 12 x In (±20 %), which means it handles high inrush currents — typical for motor or transformer loads where the D curve is the right call. Breaking capacity is 10 kA Icn at 380–415 V AC 50/60 Hz per IS/IEC 60947-2, and 15 kA Icu at 100–125 V DC. Limitation class 3 means it limits let-through energy well, which helps downstream component coordination.

DIN rail integration and wiring

Standards and environmental rating

Certified to IS/IEC 60947-2, category A, with suitability for isolation marked. Pollution degree 3, overvoltage category IV, and tropicalisation class 2 per IEC 60068-1 (handles 95 % RH at 55 °C). Electrical and mechanical durability both rated at 20,000 cycles — solid for a distribution MCB in a panel that sees occasional switching.

Frequently asked questions

Where can I buy the A9N3P06DIN and get a price?

The A9N3P06DIN is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the breaking capacity of the A9N3P06DIN?

It has a breaking capacity of 10 kA Icn at 380–415 V AC 50/60 Hz and 15 kA Icu at 100–125 V DC, both per IS/IEC 60947-2.

What does the D curve mean on this MCB?

The D curve means the magnetic trip threshold is 12 x In (±20 %), designed for loads with high inrush current such as motors, transformers, and welding equipment.

MPN
A9N3P06DIN