Skip to main content
Schneider Electric A9N3P25DIN — Miniature Circuit Breakers (MCB)

Schneider Electric A9N3P25DIN Acti9 xC60 MCB, D Curve, 25 A,

MPNA9N3P25DIN
Active

Schneider Electric Acti9 xC60, miniature circuit breaker, A9N3P25DIN, 3P, D curve, 25 A rated current, 10 kA breaking capacity at 400 V AC, clip-on 35 mm DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N3P25DIN — Identification
ParameterValue
Product nameXC60
Product rangeActi9
Product range (series)Acti9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9N3P25DIN — Ratings
ParameterValue
Rated current (In)25 A
Poles configuration3P
Number of protected poles3
Breaking capacity10 kA Inc at 380...415 V AC 50/60 Hz conforming to IS/IEC 60947-2 15 kA Icu at 100...125 V DC conforming to IS/IEC 60947-2
Rated service breaking capacity (Ics)7.5 kA conforming to IS/IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA conforming to IS/IEC 60947-2 - 100...125 V DC
Rated operational voltage (Ue)220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 100...125 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to IS/IEC 60947-2
Rated impulse withstand voltage (Uimp)4 kV conforming to IS/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to IS/IEC 60947-2
Overvoltage categoryIV
A9N3P25DIN — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to IS/IEC 60947-2
Limitation class3 conforming to IS/IEC 60947-2
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles
A9N3P25DIN — Mechanical
ParameterValue
Mounting support35 mm DIN rail
Mounting modeClip-on
Control typeToggle
Terminal connection typeTunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)
Terminal tightening torque2 N.m
Wire stripping length13 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Width54 mm
Height85 mm
Depth77.5 mm
Number of 9 mm pitches6
A9N3P25DIN — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Pollution degree3
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9N3P25DIN — Approvals
ParameterValue
StandardsIS/IEC 60947-2

Product details

Schneider Electric A9N3P25DIN — an Acti9 xC60 miniature circuit breaker, 3-pole, D curve, rated 25 A. This is the one you grab when a motor circuit or transformer primary needs a high-inrush-tolerant thermal-magnetic trip. D-curve magnetic threshold kicks at 12 x In (±20 %), so it holds through the starting surge of a 25 A-rated motor or a 6 kVA transformer without nuisance tripping, then clears a hard fault at 10 kA Icn at 380–415 V AC (15 kA Icu at 100–125 V DC). Rated for category A utilisation per IS/IEC 60947-2, pollution degree 3, overvoltage category IV — meaning it's built for the main distribution board, not a clean-room sub-panel. IP20 finger-safe terminals; separate earth-leakage block available if you need it downstream. Electrical endurance rated 10,000 cycles, mechanical 20,000.

At 100–125 V DC the Icu climbs to 15 kA, which matters for battery banks or DC bus protection. The D curve means the magnetic trip won't fire until roughly 300 A instantaneous (12 x 25 A); compare that to a C curve (5–10 x In) that could trip on a motor start. If your load is resistive or a light inductive bank, you could oversize the breaker — stick with the 25 A rating for the conductor ampacity, not the load. Width is 54 mm (6 x 9 mm pitches) — standard 3-pole modular footprint. Depth 77.5 mm, height 85 mm. Fits any 35 mm DIN rail enclosure; leave clearance above for the toggle and below for the tunnel terminal wiring. Strip 13 mm for the conductor, torque to 2 N·m.

Current production part — no end-of-life notice, no successor. If you're filling a BOM line or replacing a failed unit on a live panel, this order code is still the active factory part.

Frequently asked questions

What is the breaking capacity of the A9N3P25DIN?

10 kA Icn at 380–415 V AC 50/60 Hz, and 15 kA Icu at 100–125 V DC, both per IS/IEC 60947-2.

Where can I buy the A9N3P25DIN?

Sourced and quoted to order against an RFQ through independent distribution. Availability and pricing confirmed at quote time.

What standards does the A9N3P25DIN comply with?

Certified to IS/IEC 60947-2, pollution degree 3, overvoltage category IV, tropicalisation class 2 per IEC 60068-1.

What terminals does the A9N3P25DIN use?

Tunnel-type terminals on the bottom, accepting up to 25 mm² rigid or 16 mm² flexible. Biconnect bottom terminals also available. Wire strip length is 13 mm, tightening torque 2 N·m.

MPN