Skip to main content
Schneider Electric A9N3P50CGN — Miniature Circuit Breakers (MCB)

Schneider Electric A9N3P50CGN Acti9 xC60 MCB, 50 A, C Curve,

MPNA9N3P50CGN
Active

Schneider Electric Acti9 xC60, miniature circuit breaker, 50 A, C curve, 3P, 10 kA Icn at 240/415 V AC, clip-on 35 mm DIN rail, thermal-magnetic trip, white.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N3P50CGN — Identification
ParameterValue
Product nameXC60
Product rangeActi9
Product range (series)Acti9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9N3P50CGN — Ratings
ParameterValue
Rated current (In)50 A
Poles configuration3P
Number of protected poles3
Breaking capacity10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1 10000 A Icn at 415 V AC 50/60 Hz conforming to IS/IEC 60898-1
Rated operational voltage (Ue)220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryIV
A9N3P50CGN — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit5...10 x In
Earth-leakage protectionSeparate block
Limitation class3 conforming to IS/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles
A9N3P50CGN — Mechanical
ParameterValue
Mounting support35 mm DIN rail
Mounting modeClip-on
Control typeToggle
Terminal connection typeBiconnect (bottom) Tunnel type terminals (bottom) 25 mm² flexible Tunnel type terminals (bottom) 35 mm² rigid
Terminal tightening torque3.5 N.m
Wire stripping length13 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Width54 mm
Height85 mm
Depth77.5 mm
Number of 9 mm pitches6
A9N3P50CGN — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Pollution degree3
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9N3P50CGN — Approvals
ParameterValue
StandardsIS/IEC 60898-1

Product details

The Schneider Electric A9N3P50CGN is a 50 A, 3-pole miniature circuit breaker from the Acti9 xC60 family, built to IS/IEC 60898-1 for AC distribution in residential and light commercial panels.

Rated breaking capacity is 10 kA Icn at both 240 V and 415 V AC per IS/IEC 60898-1. That 10 kA figure is the same at both voltage levels, so you don't have to derate the interrupting rating when the breaker is used on a 415 V three-phase feed — it holds the full 10 kA across the rated voltage range of 220–240 V and 380–415 V AC. Overvoltage category IV means it's rated for the main distribution board, not just sub-panels, so it can sit at the service entrance where fault currents are highest.

Width is 54 mm (6 x 9 mm pitches), depth 77.5 mm, height 85 mm — standard 3-pole MCB footprint for a DIN-rail enclosure.

Designed and tested to IS/IEC 60898-1 for overcurrent protection in household and similar installations. Earth-leakage protection requires a separate block — this is a plain MCB, not an RCBO.

Frequently asked questions

Where can I buy the A9N3P50CGN and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time, not a stock-count promise.

What is the breaking capacity of the A9N3P50CGN?

10 kA Icn at both 240 V and 415 V AC, 50/60 Hz, per IS/IEC 60898-1. The rating holds across the full voltage range without derating.

What does the C curve mean on this breaker?

Magnetic tripping occurs between 5 and 10 times the rated current (250–500 A for this 50 A unit). That's the standard curve for general-purpose distribution where moderate inrush from motors or transformers is expected — it won't nuisance-trip on startup but clears hard faults fast.

What compliance documentation does Schneider provide for the A9N3P50CGN?

The breaker is certified to IS/IEC 60898-1. Tropicalisation per IEC 60068-1 class 2 is documented. For RoHS, REACH, and UL declarations, the manufacturer's compliance portal holds the current declarations — these are available on request with the RFQ.

MPN