Skip to main content
Schneider Electric A9N4P01CIN — Miniature Circuit Breakers (MCB)

Schneider Electric A9N4P01CIN Acti9 xC60 MCB, 4P, 1 A, C Cur

MPNA9N4P01CIN
Active

Schneider Electric Acti9 xC60 miniature circuit-breaker, A9N4P01CIN, 4 poles, 1 A, C curve, 10 kA breaking capacity at 380-415 V AC, clip-on 35 mm DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N4P01CIN — Identification
ParameterValue
Product nameXC60
Product rangeActi9
Product range (series)Acti9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9N4P01CIN — Ratings
ParameterValue
Rated current (In)1 A
Poles configuration4P
Number of protected poles4
Breaking capacity10 kA Inc at 380...415 V AC 50/60 Hz conforming to IS/IEC 60947-2 6 kA Icu at 220...250 V DC conforming to IS/IEC 60947-2
Rated service breaking capacity (Ics)7.5 kA conforming to IS/IEC 60947-2 - 380...415 V AC 50/60 Hz 6 kA conforming to IS/IEC 60947-2 - 220...250 V DC
Rated operational voltage (Ue)220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 220...250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to IS/IEC 60947-2
Rated impulse withstand voltage (Uimp)4 kV conforming to IS/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to IS/IEC 60947-2
Overvoltage categoryIV
A9N4P01CIN — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to IS/IEC 60947-2
Limitation class3 conforming to IS/IEC 60947-2
Electrical durability (cycles)20000 cycles
Mechanical durability (cycles)20000 cycles
A9N4P01CIN — Mechanical
ParameterValue
Mounting support35 mm DIN rail
Mounting modeClip-on
Control typeToggle
Terminal connection typeTunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)
Terminal tightening torque2 N.m
Wire stripping length13 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Width72 mm
Height85 mm
Depth77.5 mm
Number of 9 mm pitches8
A9N4P01CIN — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Pollution degree3
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9N4P01CIN — Approvals
ParameterValue
StandardsIS/IEC 60947-2

Product details

The Schneider Electric A9N4P01CIN is a 4-pole miniature circuit-breaker from the Acti9 xC60 family, rated at 1 A with a C-curve trip characteristic. It clips onto a 35 mm DIN rail and is designed for distribution in AC or DC networks at 50/60 Hz. The C curve means magnetic tripping occurs between 5 and 10 times the rated current — here, 8 x In ±20 % — so it handles moderate inrush from small motors or transformers without nuisance trips, while still clearing short circuits fast enough for branch protection. Breaking capacity is 10 kA at 380-415 V AC (IS/IEC 60947-2), and 6 kA at 220-250 V DC — enough for most industrial panel feeders where the upstream transformer or supply can deliver that fault current.

Clip-on mounting on a 35 mm DIN rail, 72 mm wide, occupying 8 modules of 9 mm pitch. The tunnel-type terminals accept up to 25 mm² rigid or 16 mm² flexible cable; strip length is 13 mm.

Frequently asked questions

What is the breaking capacity of A9N4P01CIN?

10 kA at 380-415 V AC (Inc per IS/IEC 60947-2) and 6 kA at 220-250 V DC (Icu per the same standard).

Where can I buy A9N4P01CIN?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is A9N4P01CIN's depth?

The depth is 77.5 mm.

What standards does A9N4P01CIN comply with?

It complies with IS/IEC 60947-2. Tropicalisation is class 2 per IEC 60068-1. Pollution degree 3, overvoltage category IV.

MPN
A9N4P01CIN