Specifications

A9N4P16DIN — Identification
ParameterValue
Product nameXC60
Product rangeActi9
Product range (series)Acti9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9N4P16DIN — Ratings
ParameterValue
Rated current (In)16 A
Poles configuration4P
Number of protected poles4
Breaking capacity10 kA Inc at 380...415 V AC 50/60 Hz conforming to IS/IEC 60947-2 6 kA Icu at 220...250 V DC conforming to IS/IEC 60947-2
Rated service breaking capacity (Ics)7.5 kA conforming to IS/IEC 60947-2 - 380...415 V AC 50/60 Hz 6 kA conforming to IS/IEC 60947-2 - 220...250 V DC
Rated operational voltage (Ue)220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 220...250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to IS/IEC 60947-2
Rated impulse withstand voltage (Uimp)4 kV conforming to IS/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to IS/IEC 60947-2
Overvoltage categoryIV
A9N4P16DIN — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to IS/IEC 60947-2
Limitation class3 conforming to IS/IEC 60947-2
Electrical durability (cycles)20000 cycles
Mechanical durability (cycles)20000 cycles
A9N4P16DIN — Mechanical
ParameterValue
Mounting support35 mm DIN rail
Mounting modeClip-on
Control typeToggle
Terminal connection typeTunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)
Terminal tightening torque2 N.m
Wire stripping length13 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Width72 mm
Height85 mm
Depth77.5 mm
Number of 9 mm pitches8
A9N4P16DIN — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Pollution degree3
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9N4P16DIN — Approvals
ParameterValue
StandardsIS/IEC 60947-2

Product details

The Schneider Electric A9N4P16DIN is an Acti9 xC60 miniature circuit breaker rated 16 A with a D tripping curve, 4 poles, and a breaking capacity of 10 kA Icn at 380–415 V AC 50/60 Hz per IS/IEC 60947-2. At 220–250 V DC it breaks 6 kA Icu. The D curve means magnetic trip occurs at 12 x In (±20 %), so it handles high inrush loads like motor starters and transformers without nuisance tripping. IP20 finger-safe terminals suit enclosed distribution boards.

Suitability for isolation is confirmed per the same standard.

Frequently asked questions

What is the breaking capacity of A9N4P16DIN?

10 kA Icn at 380–415 V AC 50/60 Hz and 6 kA Icu at 220–250 V DC, both per IS/IEC 60947-2.

Where can I buy A9N4P16DIN?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What is the D curve trip threshold on this breaker?

Magnetic tripping occurs at 12 x In (±20 %), so at 16 A rated current the magnetic trip starts around 192 A.