Skip to main content
Schneider Electric A9N4P32CIN — Miniature Circuit Breakers (MCB)

Schneider Electric A9N4P32CIN Acti9 xC60 MCB, 32 A, 4P, C-Cu

MPNA9N4P32CIN
Active

Schneider Electric Acti9 xC60, miniature circuit breaker, 4P, 32 A, C-curve, 10 kA at 415 V AC, thermal-magnetic, clip-on 35 mm DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N4P32CIN — Identification
ParameterValue
Product nameXC60
Product rangeActi9
Product range (series)Acti9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9N4P32CIN — Ratings
ParameterValue
Rated current (In)32 A
Poles configuration4P
Number of protected poles4
Breaking capacity10 kA Inc at 380...415 V AC 50/60 Hz conforming to IS/IEC 60947-2 6 kA Icu at 220...250 V DC conforming to IS/IEC 60947-2
Rated service breaking capacity (Ics)7.5 kA conforming to IS/IEC 60947-2 - 380...415 V AC 50/60 Hz 6 kA conforming to IS/IEC 60947-2 - 220...250 V DC
Rated operational voltage (Ue)220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 220...250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to IS/IEC 60947-2
Rated impulse withstand voltage (Uimp)4 kV conforming to IS/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to IS/IEC 60947-2
Overvoltage categoryIV
A9N4P32CIN — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to IS/IEC 60947-2
Limitation class3 conforming to IS/IEC 60947-2
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles
A9N4P32CIN — Mechanical
ParameterValue
Mounting support35 mm DIN rail
Mounting modeClip-on
Control typeToggle
Terminal connection typeBiconnect (bottom) Tunnel type terminals (bottom) 25 mm² flexible Tunnel type terminals (bottom) 35 mm² rigid
Terminal tightening torque3.5 N.m
Wire stripping length13 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Width72 mm
Height85 mm
Depth77.5 mm
Number of 9 mm pitches8
A9N4P32CIN — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Pollution degree3
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9N4P32CIN — Approvals
ParameterValue
StandardsIS/IEC 60947-2

Product details

The Schneider Electric A9N4P32CIN is an Acti9 xC60 miniature circuit breaker with a 32 A rated current, 4 protected poles, and a C-curve trip characteristic. It's a thermal-magnetic unit rated for distribution duty in 50/60 Hz networks, with a breaking capacity of 10 kA Icn at 380–415 V AC and 6 kA Icu at 220–250 V DC, both per IS/IEC 60947-2. Clip-on mounting to a 35 mm DIN rail, 72 mm wide, 85 mm tall, 77.5 mm deep — fits standard distribution boards. Toggle control with ON/OFF visual indication.

Compliance documentation is standard for the Acti9 line: IS/IEC 60947-2 certification covers the breaking capacity and utilization category A. Limitation class 3 per IS/IEC 60947-2 for energy let-through. Suitability for isolation marked yes per the same standard.

Integration Notes

The biconnect bottom terminals let you loop feed-through without an extra busbar. Earth-leakage protection requires a separate block — not integrated. Electrical durability rated 10,000 cycles, mechanical 20,000 cycles — fine for distribution duty where the breaker sees infrequent manual switching. For high-cycle motor starting, consider a contactor instead.

Frequently asked questions

How do I get current pricing and availability for A9N4P32CIN?

Submit an RFQ through the storefront. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is A9N4P32CIN's breaking capacity at 415 V AC?

10 kA Icn at 380–415 V AC 50/60 Hz per IS/IEC 60947-2. At 220–250 V DC it's 6 kA Icu.

What compliance standards does A9N4P32CIN meet?

Certified to IS/IEC 60947-2. Tropicalisation class 2 per IEC 60068-1. Limitation class 3 per IS/IEC 60947-2. Suitability for isolation marked yes.

MPN