Schneider Electric A9P44716
MPNA9P44716
Active
A9P44716 - IC40N 3P+N B 16A 6000A by SQUARE D
$95.25Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Control type | Toggle |
| Network type | AC |
| Product or component type | Miniature circuit-breaker |
| Voltage | 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| [Ue] rated operational voltage | 400 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 4 kV conforming to EN/IEC 60947-2 |
| Breaking capacity | 10 kA Icu at 400 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 |
| Current | 16 A |
| [Ics] rated service breaking capacity | 6000 A 100 % x Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 7.5 kA 75 % x Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Network frequency | 50/60 Hz |
| Poles description | 3P + N |
| Number of protected poles | 3 |
All specifications
| Parameter | Value |
|---|---|
| IP degree of protection | IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529 |
| Mounting mode | Clip-on |
| Mounting support | DIN rail |
| Wire stripping length | 14 mm for top or bottom connection |
| Connections - terminals | Tunnel type terminals top or bottom 1...10 mm² flexible Tunnel type terminals top or bottom 1...16 mm² rigid |
| Pollution degree | 3 conforming to EN/IEC 60947-2 |
| Relative humidity | 95 % at 55 °C |
| Operating altitude | 2000 m |
| Depth | 74 mm |
| Width | 54 mm |
| Color | White |
| Height | 85 mm |
| Electrical durability | 20000 cycles |
| Mechanical durability | 20000 cycles |
| Standards | EN/IEC 60898-1 EN/IEC 60947-2 |
| Range | Acti9 |
| Curve code | B |
| 9 mm pitches | 6 |
| Quality labels | IMQ OVE |
| Limitation class | 3 conforming to EN/IEC 60898-1 |
| Local signalling | ON/OFF indication Trip indicator |
| Neutral position | Left |
| Device short name | iC40N |
| Tightening torque | 2 N.m top or bottom |
| Device application | Distribution |
| Trip unit technology | Thermal-magnetic |
| Magnetic tripping limit | 3...5 x In conforming to EN/IEC 60898-1 4 x In +/- 20 % conforming to EN/IEC 60947-2 |
| Earth-leakage protection | Separate block |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Contact position indicator | Yes |
| Locking options description | Padlocking device |
| Ambient air temperature for storage | -40...85 °C |
| Ambient air temperature for operation | -25...70 °C |
MPN