Skip to main content
Schneider Electric A9R11280S — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9R11280S Acti9 iID RCCB, 80 A, 30 mA, Ty

MPNA9R11280S
Active

Schneider Electric Acti9 iID, residual current circuit breaker (RCCB), 2P, 80 A, 30 mA, Type AC, 220-240 V AC, clip-on DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9R11280S — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
A9R11280S — Electrical Ratings
ParameterValue
Rated current (In)80 A
Rated operational voltage (Ue)220...240 V AC 50/60 Hz
Poles description2P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Device location in systemOutgoer
Electrical durabilityAC-1: 10000 cycles
Mechanical durability (operating cycles)20000 cycles
A9R11280S — Identification
ParameterValue
Product nameActi9 iID
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameiID
A9R11280S — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsSingle terminal top or bottom 1...35 mm² rigid Single terminal top or bottom 1...25 mm² flexible Single terminal top or bottom 1...25 mm² flexible with ferrule
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width36 mm
Height91 mm
Depth73.5 mm
A9R11280S — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
A9R11280S — Approvals
ParameterValue
StandardsEN/IEC 61008-1 EN/IEC 61008-2-1

Product details

The Schneider Electric A9R11280S is an Acti9 iID residual current circuit breaker (RCCB) — a 2-pole, voltage-independent device rated 80 A with 30 mA earth-leakage sensitivity, Type AC, for 220-240 V AC 50/60 Hz networks.

The 80 A rated current (In) sets the continuous load capacity — sized for main incoming or large subfeed circuits, not branch lighting. The 30 mA sensitivity is the standard for personal protection against indirect contact; it trips on sinusoidal AC earth faults only (Type AC), so it is not suitable for circuits with pulsed DC or variable-speed drives that generate smooth DC fault currents. Rated insulation voltage (Ui) is 500 V AC, and impulse withstand (Uimp) is 6 kV, so the device is coordinated for standard overvoltage Category III environments.

Neutral is on the left. Terminals accept up to 35 mm² rigid or 25 mm² flexible cable, with a stripping length of 14 mm and tightening torque of 3.5 N·m. The toggle control and padlocking option allow local lockout-tagout.

Frequently asked questions

What are the key ratings of A9R11280S?

80 A rated current, 30 mA earth-leakage sensitivity, Type AC, 2-pole, 220-240 V AC 50/60 Hz, breaking capacity 1500 A, instantaneous trip, voltage-independent operation.

What standards does A9R11280S comply with?

It complies with EN/IEC 61008-1 and EN/IEC 61008-2-1 for residual current circuit breakers. Impulse withstand is tested to 8/20 µs, 250 A per those standards.

Where can I buy A9R11280S?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
A9R11280S