Skip to main content
Schneider Electric A9TDNC616 — Residual Current Breakers (RCCB/RCBO)

Schneider A9TDNC616 Acti9 iCV40N ARC, 16 A, 6 kA, C-curve

MPNA9TDNC616
Active

Schneider Electric Acti9 Active iCV40N ARC RCBO, 1P+N, 16 A, C-curve, 6 kA Icn at 230 V AC, DIN-rail clip-on, white (RAL 9003).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9TDNC616 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A-SI (Super Immunised)
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip LED arc fault diagnostic
A9TDNC616 — Electrical Ratings
ParameterValue
Rated current (In)16 A
Rated operational voltage (Ue)230 V AC 50 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)250 V AC 50 Hz between phase and neutral
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII
Device location in systemOutgoer
Electrical durability20000 cycles 230 V AC 50 Hz
Mechanical durability (operating cycles)20000 cycles
A9TDNC616 — Identification
ParameterValue
Product nameActi9 Active iCV40 ARC
Product / component typeActive arc fault detection RCBO
Product range / familyActi9
Device short nameiCV40N ARC
A9TDNC616 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminal 1...16 mm² rigid Tunnel type terminal 1...10 mm² flexible
Wire stripping length14 mm
Terminal tightening torque2 N.m
Width36 mm
Height91 mm
Depth73 mm
A9TDNC616 — Environmental
ParameterValue
Operating ambient temperature-25...50 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree2 conforming to EN/IEC 62606
Relative humidity95 % at 55 °C
Operating altitude2000 m
TropicalisationSeverity B conforming to IEC 60068-2-30 for 28 d
A9TDNC616 — Approvals
ParameterValue
StandardsEN/IEC 62606 EN/IEC 61009-1 EN/IEC 61009-2-1

Product details

The Schneider Electric A9TDNC616 is an Acti9 Active iCV40N ARC residual current circuit breaker with integral overcurrent protection (RCBO) in a 1P+N format, rated at 16 A with a C-curve trip characteristic. The breaking capacity is 6000 A Icn at 230 V AC 50 Hz, certified to EN/IEC 61009-2-1, which covers the majority of domestic and commercial fault-level requirements in 230 V networks. This unit also carries arc-fault detection (AFDD) per EN/IEC 62606, adding series and parallel arc-fault protection on top of the thermal-magnetic and residual-current elements. The local signalling includes a fault-trip LED and an arc-fault diagnostic indicator, which helps a field technician identify the cause of a trip without additional test gear.

The part is listed with a targeted country of India, but the EN/IEC certifications (EN/IEC 62606, EN/IEC 61009-1, EN/IEC 61009-2-1) make it acceptable in any jurisdiction that recognises those standards. For UL-listed installations, verify local acceptance of the IEC marking.

Cable entry from top or bottom, with a wire stripping length of 14 mm and a tightening torque of 2 N·m. Tropicalisation severity B per IEC 60068-2-30 for 28 days is standard, so the unit holds up in high-humidity environments (95 % RH at 55 °C).

Electrical performance and metering

Built-in measurement of voltage, current, active power, and power factor with stated accuracies of ±2 % for voltage and current, ±5 % for power. This allows the RCBO to double as a basic energy-monitoring point in the distribution board without a separate meter. Total power losses are 3.408 W (2.65 W per pole). Electrical durability is 20,000 cycles at 230 V AC 50 Hz, matching the mechanical durability of 20,000 cycles. Limitation class 3 means the device limits let-through energy well in a fault event.

Frequently asked questions

Where can I buy A9TDNC616 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing.

What is A9TDNC616's breaking capacity?

6000 A Icn at 230 V AC 50 Hz, certified to EN/IEC 61009-2-1.

What standards does A9TDNC616 comply with?

It complies with EN/IEC 62606 (arc-fault detection), EN/IEC 61009-1, and EN/IEC 61009-2-1 (RCBO).

What is the width of A9TDNC616?

36 mm (2 modules at 9 mm pitch), clip-on DIN-rail mount.

MPN
A9TDNC616