Skip to main content
Schneider Electric A9TDND610 — Residual Current Breakers (RCCB/RCBO)

Schneider A9TDND610 Acti9 iCV40H ARC, 10 A, 10 kA, C-curve

MPNA9TDND610
Active

Schneider Electric Acti9 Active iCV40 ARC arc-fault detection device, 1P+N, 10 A, C-curve, 10 kA Icn at 230 V AC, thermal-magnetic trip, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9TDND610 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A-SI (Super Immunised)
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip LED arc fault diagnostic
A9TDND610 — Electrical Ratings
ParameterValue
Rated current (In)10 A
Rated operational voltage (Ue)230 V AC 50 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)250 V AC 50 Hz between phase and neutral
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII
Device location in systemOutgoer
Electrical durability20000 cycles 230 V AC 50 Hz
Mechanical durability (operating cycles)20000 cycles
A9TDND610 — Identification
ParameterValue
Product nameActi9 Active iCV40 ARC
Product / component typeActive arc fault detection RCBO
Product range / familyActi9
Device short nameiCV40H ARC
A9TDND610 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminal 1...16 mm² rigid Tunnel type terminal 1...10 mm² flexible
Wire stripping length14 mm
Terminal tightening torque2 N.m
Width36 mm
Height91 mm
Depth73 mm
A9TDND610 — Environmental
ParameterValue
Operating ambient temperature-25...50 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree2 conforming to EN/IEC 62606
Relative humidity95 % at 55 °C
Operating altitude2000 m
TropicalisationSeverity B conforming to IEC 60068-2-30 for 28 d
A9TDND610 — Approvals
ParameterValue
StandardsEN/IEC 62606 EN/IEC 61009-1 EN/IEC 61009-2-1

Product details

Arc-fault detection device, 10 A, C-curve

The Schneider A9TDND610 is an Acti9 Active iCV40 ARC arc-fault detection device (AFDD) combining overcurrent protection and arc-fault detection in a single 1P+N module.

The 10 kA breaking capacity (H code) gives enough fault-current headroom for most final sub-circuits in India (the targeted country per the spec), where typical prospective short-circuit currents stay under 6 kA. Measurement accuracy is specified at ±2 % for voltage and current, ±5 % for power — this is the built-in metering function that lets the device report line conditions locally via the LED signalling (ON, OFF, fault trip, arc-fault diagnostic). The arc-fault detection itself follows EN/IEC 62606, which means it discriminates between harmless arcs (switch arcing, motor brushes) and dangerous series/parallel arcs that cause fires.

Cable entry is top and bottom, with a wire stripping length of 14 mm and a tightening torque of 2 N·m for the terminals. Tropicalisation to severity B (28 days per IEC 60068-2-30) means it handles the humidity and condensation cycles typical of coastal or monsoon-exposed panels without internal corrosion.

Frequently asked questions

How do I get pricing and availability for A9TDND610?

The A9TDND610 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for your quantity and delivery timeline.

What is the breaking capacity of A9TDND610?

The A9TDND610 has a breaking capacity of 10000 A Icn at 230 V AC 50 Hz, conforming to EN/IEC 61009-2-1. The H code indicates this is the high-breaking-capacity variant within the iCV40 family.

What standards does A9TDND610 comply with?

The A9TDND610 complies with EN/IEC 62606 (arc-fault detection devices), EN/IEC 61009-1 (residual current operated circuit-breakers with integral overcurrent protection), and EN/IEC 61009-2-1 (general rules for RCBOs). Pollution degree 2 per EN/IEC 62606 applies.

MPN