Rated 13 A with a B curve (magnetic trip 3...5 × In), it clips onto DIN rail and fits a 36 mm width — four 9 mm pitches. Breaking capacity is 3 kA Icn at 230 V AC per EN/IEC 60898-1, 6 kA Icn at 230 V AC per the same standard, and 10 kA Icu at 230 V AC per EN/IEC 60947-2, covering both residential and industrial coordination requirements.
Clip-on mounting to DIN rail (35 mm) with tunnel-type terminals accepting 1...16 mm² rigid or 1...10 mm² flexible wire. Cable entry from top and bottom; neutral position left. IP20 finger-safe protection suits enclosed panel installation.
Local signalling includes ON/OFF toggle, fault-trip LED, and arc-fault diagnostic LED. Tropicalisation severity B per IEC 60068-2-30 for 28 days. Electrical durability 10,000 cycles, mechanical 20,000 cycles.