Skip to main content
Schneider Electric A9V82263 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9V82263 Vigi iC65 ELM 2P 63A 300mA AC-ty

MPNA9V82263
Obsolete

Schneider Electric Acti9 Vigi iC65 ELM, add-on residual current device, 2P, 63 A, 300 mA AC-type, voltage independent, clip-on DIN rail, 4 module pitches.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9V82263 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Local signalling / indicationTrip indicator
A9V82263 — Electrical Ratings
ParameterValue
Rated current (In)63 A
Rated operational voltage (Ue)230/400 V AC 50 Hz conforming to GB 16917.21
Poles description2P
Network typeAC
Network frequency50/60 Hz
Device location in systemOutgoer
A9V82263 — Identification
ParameterValue
Product nameActi9 Vigi iC60
Product / component typeAdd-on residual current device
Product range / familyActi9
Device short nameVigi iC65
A9V82263 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Width in 9 mm modules4
Width72 mm
Height101 mm
Depth73.5 mm
A9V82263 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
IP degree of protectionIP20 B
A9V82263 — Approvals
ParameterValue
StandardsGB 16917.21

Product details

The Schneider Electric A9V82263 is an Acti9 Vigi iC65 ELM add-on residual current device (RCD) — a voltage-independent, 2-pole unit rated at 63 A with 300 mA AC-type earth-leakage sensitivity.

Mounts via clip-on to a standard DIN rail, occupying 4 module pitches (72 mm wide, 101 mm tall, 73.5 mm deep). Rated for -5 to 60 °C ambient operation, so it handles warm cabinet interiors near the top of a distribution board.

The 300 mA AC-type sensitivity is instantaneous (no time delay), designed for general-purpose earth-leakage protection on outgoing circuits where equipment leakage is low and nuisance tripping is unlikely. Voltage-independent tripping means it clears a fault even if the line voltage collapses — a safety advantage over electronically latched RCDs. Rated for 230/400 V AC 50/60 Hz networks, compliant with GB 16917.21.

Frequently asked questions

Where can I buy A9V82263?

The A9V82263 is sourced through independent distribution channels. Submit an RFQ for current availability and pricing — each order is quoted on request against the available surplus or new-old-stock inventory.

What is the closest alternative to A9V82263?

No official pin-compatible or direct replacement order code has been published by Schneider Electric. For a functionally similar Acti9 Vigi iC65 RCD, review the current Acti9 catalog for active 2P 63A 300mA AC-type units — but verify terminal layout and module pitch against your existing panel layout.

What are the key ratings of A9V82263?

Rated at 63 A, 300 mA AC-type earth-leakage sensitivity, 230/400 V AC, 50/60 Hz. Instantaneous trip, voltage-independent tripping technology. 2 poles, 4 module pitches, clip-on DIN rail mount.

MPN
A9V82263