Schneider Electric A9Z02240 — Residual Current Breakers (RCCB/RCBO)

A9Z02240 Acti9 ID K RCCB, 40A, 30mA, Type A, 2P

MPNA9Z02240
Active

Schneider Electric Acti9 ID K RCCB, 40 A, 30 mA, Type A, 2-pole, 220-240 V AC, DIN-rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9Z02240 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
A9Z02240 — Electrical Ratings
ParameterValue
Rated current (In)40 A
Rated operational voltage (Ue)220...240 V AC 50 Hz
Poles description2P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)440 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durabilityAC-1: 2000 cycles
Mechanical durability (operating cycles)5000 cycles
A9Z02240 — Identification
ParameterValue
Product nameActi9 ID K
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameID K
A9Z02240 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsBiconnect top or bottom 1...35 mm² rigid Biconnect top or bottom 1...25 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width36 mm
Height81 mm
Depth68 mm
A9Z02240 — Environmental
ParameterValue
Operating ambient temperature-5...40 °C
Storage ambient temperature-30...70 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree2
A9Z02240 — Approvals
ParameterValue
StandardsEN/IEC 61008-1 EN/IEC 61008-2-1

Product details

The A9Z02240 is a 2-pole (2P) residual current circuit breaker (RCCB) from the Acti9 ID K series, rated 40 A at 220-240 V AC, 50/60 Hz. The 30 mA earth-leakage sensitivity covers personnel protection (hand-to-hand or hand-to-ground faults) per EN/IEC 61008-1. Type A detection handles sinusoidal AC and pulsating DC residual currents — the standard choice for circuits with single-phase rectified loads like switched-mode power supplies or electronic ballasts. Voltage-independent tripping means the RCCB disconnects even if the line voltage collapses — no auxiliary supply needed. Instantaneous response (no intentional delay) suits it for outgoer circuits where nuisance tripping from transient surges is not a concern; the 8/20 µs impulse withstand of 200 A gives some margin against lightning-induced spikes. Rated breaking and making capacity is 500 A (Idm and Im), adequate for most final-distribution faults.

Deployment context

The 1...35 mm² range covers most final subfeed conductors up to 40 A.

Frequently asked questions

Where can I buy A9Z02240 and how do I get a price?

The A9Z02240 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm offer.

What is A9Z02240's listed depth?

The depth is 68 mm, width 36 mm (4 module pitches), height 81 mm.

What compliance documentation does the A9Z02240 carry?

It is certified to EN/IEC 61008-1 and EN/IEC 61008-2-1, carries VDE quality label, and has IP20/IP40 ingress protection per IEC 60529.

MPN