The Schneider Electric A9Z10225 is an Acti9 iID residual current circuit breaker (RCCB) — a 2-pole, 25 A, 10 mA sensitivity unit that trips instantaneously on earth leakage.
Clip-on DIN rail mount, 36 mm wide (4 x 9 mm pitches). IP20 body, IP40 in a modular enclosure — fine for a dry indoor panel, not for washdown zones.
Type AC earth-leakage protection means it detects sinusoidal AC residual currents only — no pulsed DC or smooth DC. Voltage-independent trip coil, so it clears a fault even if the phase voltage drops. Rated insulation voltage 500 V AC, operational voltage 220…240 V AC at 50/60 Hz. Impulse withstand 6 kV, surge current 250 A (8/20 µs). Electrical endurance 15,000 cycles AC-1; mechanical 20,000 cycles. Compliance to EN/IEC 61008-1 and 61008-2-1.