Rated 63 A continuous on a 380–415 V AC 50/60 Hz network, it covers the main incoming supply for a three-phase distribution board in a panel or sub-distribution unit. The 100 mA sensitivity is the standard choice for general protection against indirect contact in commercial and industrial installations where the earth-fault loop impedance is low enough to clear a fault within the disconnection time required by EN/IEC 61008-1.
Clip-on mount to a DIN rail, 72 mm wide (8 x 9 mm pitches), 91 mm tall, 73 mm deep. Neutral on the left. Torque to 3.5 N·m. IP20 on the body, IP40 inside a modular enclosure. The toggle control and padlocking provision let you lock out for isolation during maintenance.
The iID family is Schneider's standard RCCB line in the Acti9 range, widely specified across European and Middle Eastern projects.